Page 359 - V16 Catalogue Final
P. 359

AF CONTACTORS
         4 TO 200kW


                                             4 POLE - 4NO CONTACTORS

        Features:                               400V AC-3  400V AC-3    AC-1          Auxiliary                  CONTACTORS &
        - 4 Pole.                                 (kW)        (A)        (A)       NO        NC    Part No.       OVERLOADS
        - Add-on auxiliary contact.           DIN or Panel Mount
        - Built-in surge suppression.              4          9          25         0         0    AF094000    1)
        - Reduced panel energy consumption.                                                                  1)
        - Very distinct closing and opening.      7.5         18         30         0         0    AF164000
        - Can withstand short voltage dips and voltage sags.  11  21.2   45         0         0    AF264000    1)
        - DIN or Panel mounting. AF09...AF80.     11         21.2        55         0         0    AF384000    1)
        - For connection with built-in cable clamps  18.5     40         70         0         0    AF404000    1)
           AF116...AF140.                         22          53         100        0         0    AF524000    1)
        - Panel mounting. AF116...AF370
                                                  37          80         125        0         0    AF804000    1)
                                              Panel Mount
                                                  55         116         160        0         0    AF1164000
                                                  75         140         200        0         0    AF1404000
                                                  90         190         275        0         0    AF1904000
                                                  110        205         350        0         0    AF2054000
                                                  132        265         400        0         0    AF2654000
                                                  160        305         500        0         0    AF3054000
                      AF094000...                 200        370         525        0         0    AF3704000


                                                To complete Part Number, add the required voltage code:
                                              Code         11                  13              14
                                              Control Voltages  24…60V AC / 20…60V DC  100...250V AC/DC  250...500V AC/DC
                                             1) 11 (24..60V AC/20..60V DC) arrangement not suitable for direct control by PLC-output.
                                             - Other coil voltages and auxiliary contact arrangements available.
                                             - For B version (bar connections) order standard version and remove terminals.

                      AF804000...







                                             4 POLE - 2NO/2NC CONTACTORS

                                                 400V AC-3    400V AC-3      AC-1        Auxiliary
                                                   (kW)          (A)          (A)      NO     NC   Part No.
                                                    4            9            25        0      0   AF092200    1)
                                                   7.5          18            30        0      0   AF162200    1)
                                                   11           21.2          45        0      0   AF262200    1)
                                                   11           21.2          55        0      0   AF382200    1)
                                                   18.5         40            70        0      0   AF402200    1)
                                                   37           80           125        0      0   AF802200    1)
                       AF092200...
                                                To complete Part Number, add the required voltage code:
                                              Code         11                 13                 14
                                              Control Voltages  24…60V AC / 20…60V DC  100…250V AC/DC  250…500V AC/DC
                                             1) 11(24..60VAC/20..60VDC) not suitable for direct control by PLC-output.
                                             - Other coil voltages and auxiliary contact arrangements available.




                       AF802200...






        Phone: 1300 556 601                            www.ipd.com.au                               V16-IC-C&O-R04  351