Page 103 - MCCB-XT2-XT4
P. 103

ABB | SACE Tmax XT

       3 - Class 1 Power & Energy Metering



               List and performance Presence of the  Class 1 Power & Energy Metering package allows higher measuring accuracy to be
                                    obtained for the following quantities:
                                                                                                        Accuracy of
                                     Measurement           Monitor time (min-max) Normal operating range
                                                                                                        read value
                                                                                 Standard IEC 61557-12,
                                     Phase currents  (8)   0,004 ÷ 64 In                                0,5 %   (1)
                                                                                 tables 20-22
                                     Internal earth fault current                Standard IEC 61557-12,      (1)
                                     (2)                   0,08 ÷ 64 In          table 20               0,5 %
                                     Line frequency        30 ÷ 80 Hz   (3)      fn ± 10 %   (4)        ± 0,02 Hz
                                     Total active and apparent   |Pmin ÷ Pmax|  (5)  Standard IEC 61557-12,   1 %   (1)
                                     power                                       tables 8-11-14
                                     Active and apparent phase         (5)       Standard IEC 61557-12,     (1)
                                     power                 |Pmin ÷ Pmax|         tables 8-11-14         1 %
                                     Total active and apparent   1 kWh ÷ 2 TWh; 1 kVARh ÷ 2  Standard IEC 61557-12,    (1)
                                     energy                TVARh; 1 kVAh ÷ 2 TVAh  tables 8-11-14       1 %
                                                                                 Standard IEC 61557-12,
                                     Power factor          0,5 ÷ 1                                      1%   (1)
                                                                                 table 27
                                    (1)  the accuracy values refer to the normal operating intervals and conditions established by IEC
                                    61557-12, for each quantity and class declared
                                    (2)  available with LSIG versions
                                    (3)  available for voltage values of over 30 V (with Un < 277 V) or 60 V (with Un ≥ 277 V)
                                    (4)  47 ÷ 55 Hz with fn = 50 Hz; 54 ÷ 66 Hz with fn = 60 Hz
                                    (5)  Pmin = 0,5 In x 5 V; Pmax= 3 x 16 In x 900 V
                                    (8)  internal phase current; in the presence of an external Neutral, the accuracy of current Ne is 1%

           Functional characteristics The measuring performance of the  Class 1 Power & Energy Metering package is guaranteed in the
                                    following conditions (from table 43 of standard IEC 61557-12):
                                     Characteristic                     Value
                                     Classification of performance measuring
                                     and monitoring device (PMD) in accordance  PMD-DD
                                     with chapter 4.3 of the standard
                                                                        Operating: T= -25°C to +70°C; Storage: T = -30°C to
                                     Temperature
                                                                        +70°C; Class: K70
                                                                        Up to 90% relative humidity without condensation;
                                     humidity and altitude
                                                                        From 0 to 2000 meters
                                     Performance class for active energy and   1
                                     power




                   Information page Presence of the Class 1 Power & Energy Metering package activates the IEC 61557-12 information page,
                                    which can be consulted in the About menu
                                    The page shows the activation state of the  Class 1 Power & Energy Metering package (Activated/
                                    Deactivated) and the serial numbers of certain accessories installed on the CB for the specific purpose of
                                    conforming to the characteristics of the package (electronic units and internal current sensors)





















       101 | © 2022 ABB |  1SDH002031A1002 - ECN000212994         Ekip Touch - Measurements | 3 - Class 1 Power & Energy Metering