Page 16 - MCCB-XT2-XT4
P. 16

ABB | SACE Tmax XT

       4 - Operating features



                       Introduction Ekip Touch has been developed and certified to function in specific environmental, electrical and
                                    mechanical conditions; full details are available in the Technical catalog (page 4).
                                    The following sections describe the electrical and power supply characteristics that enable Trip unit and
                                    the relative electronic accessories to operate correctly.



            Electrical characteristics The Ekip Touch measurement and protection functions described in this document are provided with
                                    primary voltage and current values within the following nominal ranges:
                                     Parameter                      Operating limits
                                     Primary current (line-to-line)  0,004 ÷ 16 In  (1)
                                     Primary voltage (line-to-line)  0 ÷ 690 V AC
                                     Rated frequency                45 ... 55 Hz (with fn= 50 Hz) / 54 ... 66 Hz (with fn= 60 Hz)
                                     Peak factor                    Complying with standard IEC 60947-2

                                    (1)  based on each phase; In refers to the nominal size of the Trip unit, available in models from 40 A
                                    to 250 A

                                    Ekip Touch can self-supply itself directly from the internal current sensors:
                                     Parameter                              Operating limits
                                     Minimum three-phase turn-on current    > 0,2 In




              Auxiliary power supply Ekip Touch can be connected to an external auxiliary supply source, which is useful when certain functions
                                    such as communication via Local Bus, recording manual operations, certain measurements and the
                                    datalogger must if available.
                                    The auxiliary supply can be provided by modules from the  Ekip Supply range (further details about
                                    operation are given on page 123) or by direct connection to the lateral terminal box.
                                    Direct connection must guarantee the following operating conditions:
                                     Parameter                              Operating limits
                                     Voltage                                24 V DC galvanically isolated
                                     Tolerance                              ±10%
                                     Maximum ripple                         ±5%
                                     Maximum inrush current @ 24 V          10 A per 5 ms
                                     Maximum rated power @ 24 V             4 W
                                                                            Insulated with grounding cable (same
                                     Connection cable
                                                                            characteristics as Belden 3105A/B or higher)
                                           IMPORTANT: if connection is direct, the power supply must be galvanically insulated and
                                           provide the insulation characteristics established by standard IEC 60950 (UL 1950) or
                                           equivalent.

























       14 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                           Trip unit Overview | 4 - Operating features