PTC Protection Function
PTC protects the motor against overtemperatures.
The Trip unit receives the alarm from the Ekip CI module to which a thermocouple can be connected for
the purpose of monitoring the temperature of the motor: the protection sends a TRIP command if the
temperature measured exceeds 120 °C for more than one second.
Parameters
Parameter Description Default
Activates/deactivates the protection and its availability in the
Enable OFF
parameters menu
Activates/deactivates transmission of the open command: if
Trip Enable disabled, the alarm and exceedance of protection time are only OFF
managed as information
66 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Protections | 9 - Motor protections