ABB | SACE Tmax XT

       7 - ROCOF protections
                                    The ROCOF Protection package can be configured in all models as additional SW package.
                                    The protection is described below:


                  ROCOF Protection Function
                                    ROCOF protection protects against rapid frequency variations: the protection sends a TRIP command if
                  t                 the frequency changes faster than control variation f28 set in the unit for longer than t28.
                       f28    ROCOF

                                            f(Hz)                              Frequency variation
                            t28
                                                                               after failure (1)
                               Hz/s                  Frequency fluctuation
                                                     (after a failure)
                                                                                              f28
                                              f mis







                                                                                    t28          t(s)

                                    Figure 22
                                    (1)  example with positive linear variation of the higher frequency of the set f28 value; the protection
                                    also manages negative variations

                                    The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 77)
                                     •  the graph with trip curve (page 92)
                                    Parameters
                                     Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the
                                     Enable                                                             OFF
                                                parameters menu
                                                Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                information
                                                establishes the maximum admissible frequency variation rate over
                                     Threshold   time; the protection trips if this rate is exceeded.   0,6 Hz/s
                                     f28        The value is given as absolute value (Hz/s) Fn) and can be set within
                                                the range: 0.4 Hz/s to 10 Hz/s in 0.2 Hz/s steps
                                     Trip       Establishes whether the protection monitors an increase (Up), a   Up or Down
                                     Direction  decrease (Down) or both variations (Up and Down)
                                                This is the trip time of the protection; the value is given in seconds
                                     Time f28                                                           0,5 s
                                                and can be set within a range: 0.06 s to 300 s, in 0.01 s steps
                                    Limitations and additional functions