Page 96 - MCCB-XT2-XT4
P. 96
ABB | SACE Tmax XT
Ekip Touch - Measurements
1 - Standard Measurements
List The Standard measurements are:
Parameter Description Page
Phase current and earth fault measurements in real
Instantaneous currents 94
time
List of events, status changes, alarms, recorded by
Events 94
the Trip unit
Trip List of current protection trips (TRIP) 94
History of minimum and maximum currents,
Min-Max measurements 96
recorded at a settable interval
Maintenance CB status: contact wear and last maintenance 97
Operation counters Number of mechanical and electrical operations 97
Instantaneous currents The instantaneous currents, available in the Main page and Summary pages, are real time measurements
of the phase and earth fault currents expressed in root mean square value; the monitor time and
performance depend on the rated current defined by the nominal size of the Trip unit:
Monitor time Normal operating Accuracy of value
Measurement
(min-max) range read (1)
Phase currents 0,004 ÷ 64 In 0,2 ÷ 1,2 In 1% (3)
Earth fault current (2) 0,08 ÷ 64 In 0,2 ÷ 1,2 In 2 % (3)
(1) the accuracies refer to normal operating ranges, as established by IEC 61557-12
(2) available with LSIG versions
(3) accuracies based on Ekip Touch and Ekip Touch Measuring without Class 1 Power & Energy
Metering package; if the Class 1 Power & Energy Metering package is present and for all other trip
unit models, check the indicated performance values from page 101
Special representations
Type of measure- Measurement < min Measurement < max “_ _ _” displayed:
ment value value (not available) due to
Phase and earth fault . . . . [64 In] (1) Sensors disconnected
currents
(1) gives the value nearest to the theoretic maximum threshold considering the measurement
resolution; example: if In=1000 A the value given is 63999 A
94 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Ekip Touch - Measurements | 1 - Standard Measurements