Page 96 - MCCB-XT2-XT4
P. 96

ABB | SACE Tmax XT
        Ekip Touch - Measurements




       1 - Standard Measurements



                               List The Standard measurements are:
                                     Parameter            Description                                Page
                                                          Phase current and earth fault measurements in real
                                     Instantaneous currents                                          94
                                                          time
                                                          List of events, status changes, alarms, recorded by
                                     Events                                                          94
                                                          the Trip unit
                                     Trip                 List of current protection trips (TRIP)    94
                                                          History of minimum and maximum currents,
                                     Min-Max measurements                                            96
                                                          recorded at a settable interval
                                     Maintenance          CB status: contact wear and last maintenance  97
                                     Operation counters   Number of mechanical and electrical operations  97



             Instantaneous currents The instantaneous currents, available in the Main page and Summary pages, are real time measurements
                                    of  the  phase  and  earth  fault  currents  expressed  in  root  mean  square  value;  the  monitor  time  and
                                    performance depend on the rated current defined by the nominal size of the Trip unit:
                                                               Monitor time     Normal operating  Accuracy of value
                                     Measurement
                                                               (min-max)        range             read  (1)
                                     Phase currents            0,004 ÷ 64 In    0,2 ÷ 1,2 In     1%  (3)
                                     Earth fault current  (2)  0,08 ÷ 64 In     0,2 ÷ 1,2 In     2 %  (3)

                                    (1)  the accuracies refer to normal operating ranges, as established by IEC 61557-12
                                    (2)  available with LSIG versions
                                    (3)  accuracies based on Ekip Touch and Ekip Touch Measuring without Class 1 Power & Energy
                                    Metering package; if the Class 1 Power & Energy Metering package is present and for all other trip
                                    unit models, check the indicated performance values from page 101

                                    Special representations
                                     Type of measure-   Measurement < min   Measurement < max   “_ _ _” displayed:
                                     ment               value               value              (not available) due to
                                     Phase and earth fault   . . . .        [64 In]  (1)       Sensors disconnected
                                     currents

                                    (1)  gives the value nearest to the theoretic maximum threshold considering the measurement
                                    resolution; example: if In=1000 A the value given is 63999 A






























       94 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                Ekip Touch - Measurements | 1 - Standard Measurements