Page 97 - MCCB-XT2-XT4
P. 97

ABB | SACE Tmax XT

                            Events Ekip Touch can record the last 200 events, mainly concerning variations in the status and operation of the
                                    unit; in particular:
                                     •  configuration status of the bus, operating mode, active set, auxiliary supply
                                     •  connection statuses or alarms: current sensors, Trip Coil
                                     •  connection statuses or alarms: current sensors, Rating Plug, Trip unit, Trip Coil
                                     •  protections: timing in progress or alarm
                                     •  trip: status of open command, signaling of trips due to protection
                                           NOTE:the first event available in the list is the most recent one; having reached the 200-events
                                           threshold, the oldest events will be progressively overwritten
                                    The complete list is available in the Measurements - Historicals - Events menu, where a set of information
                                    is given for each event: icon of the type of event, name of event, date and time recorded.
                                    There are 4 icons that identify the type of event:

                                     Icon         Description
                                                  Event reported for information purposes

                                                  Timing of a protection in progress, trip expected

                                                  Alarm referring to a non-dangerous condition

                                                  Alarm concerning operation, a fault or connection failure




                           Tripping Ekip Touch is able to record the last 30 TRIPs.
                                    The complete list is available in the Measurements - Historicals - Trips menu, where useful information is
                                    given for each trip:
                                     •  the protection that caused the trip
                                     •  the consecutive number of the trip
                                     •  the date and time of the trip (with reference to the internal clock)
                                     •  the measurements associated with the tripped protection
                                           NOTE: once the 30-TRIP threshold has been exceeded, the oldest trips are progressively
                                           overwritten
                                    Correlated measurements
                                    The type of protection involved determines the measurements recorded at the moment of tripping:
                                     Protection   Measurements recorded     Notes
                                                                            Ne is available with CBs type 4P and 3P + N; Ig is
                                     Current      L1, L2, L3, Ne, Ig Currents
                                                                            available in the case of trips due to G protection
                                     Temperature  L1, L2, L3, Ne Currents   The temperature cannot be displayed

                                    Access to most recent trips
                                    Besides being available in the Historicals menu, information about the most recent trips can be accessed
                                    in three different ways, depending on the conditions of Ekip Touch:
                                     Condition                 Access
                                                               The main page is temporarily replaced by a trip information page;
                                     Trips that have just occurred   press the iTEST button to reset and go back to the normal screen
                                     with Ekip Touch on
                                                               page
                                     Trips that have just occurred   Press the iTEST button to display the trip information page for a
                                     with Ekip Touch off       few seconds
                                     Rapid consultation in all the   Press the iTEST button four times from any page other than a
                                     other conditions          menu, or a page accessed via a menu