Page 102 - MCCB-XT5
P. 102

ABB | SACE Tmax XT
        Ekip Touch - Measurements




       1 - Standard Measurements



                               List The Standard measurements are:
                                     Parameter            Description                                Page
                                                          Phase current and earth fault measurements in real
                                     Instantaneous currents                                          100
                                                          time
                                                          List of events, status changes, alarms, recorded by
                                     Events                                                          100
                                                          the Trip unit
                                     Trip                 List of current protection trips (TRIP)    100
                                                          History of minimum and maximum currents,
                                     Min-Max measurements                                            102
                                                          recorded at a settable interval
                                     Maintenance          CB status: contact wear and last maintenance  103
                                     Operation counters   Number of mechanical and electrical operations  103



             Instantaneous currents The instantaneous currents, available in the Measurements pages, are real time measurements of the
                                    phase and earth fault currents expressed in root mean square value; the monitor time and performance
                                    depend on the rated current defined by the Rating plug (In):
                                                               Monitor time     Normal operating  Accuracy of value
                                     Measurement
                                                               (min-max)        range             read  (1)
                                     Phase currents  (4)       0,004 ÷ 64 In    0,2 ÷ 1,2 In     1%  (3)
                                     Internal earth fault current  (2)  0,08 ÷ 64 In  0,2 ÷ 1,2 In  2 %  (3)

                                    (1)  the accuracies refer to normal operating ranges, as established by IEC 61557-12
                                    (2)  available with LSIG versions
                                    (3)  accuracies based on Ekip Touch and Ekip Touch Measuring without Class 1 Power & Energy
                                    Metering package; if the Class 1 Power & Energy Metering package is present and for all other trip
                                    unit models, check the indicated performance values from page 107
                                    (4)  the higher phase currents are also available in the Histograms, Measuring instruments and
                                    Measurement summary pages

                                    Special representations
                                     Type of measure-   Measurement < min   Measurement < max   “_ _ _” displayed:
                                     ment               value               value              (not available) due to
                                     Internal earth fault and   . . . .     [64 In]  (1)       Sensors disconnected
                                     phase currents

                                    (1)  gives the value nearest to the theoretic maximum threshold considering the measurement
                                    resolution; example: if In=1000 A the value given is 63999 A




























       100 | © 2022 ABB |  1SDH002039A1002 - ECN000212994               Ekip Touch - Measurements | 1 - Standard Measurements