Page 106 - MCCB-XT5
P. 106

ABB | SACE Tmax XT

       2 - Measuring Measurements



                               List The Measuring measurements are
                                     Condition             Access                                       Page
                                                           Phase and line-to-line voltage measurements in real
                                     Instantaneous voltages                                             104
                                                           time
                                                           Real time measurements of the active, reactive,
                                     Instantaneous powers                                               104
                                                           apparent phase and total powers
                                     Instantaneous frequency  Measurement of the line frequency         104
                                                           List of trips (TRIP) due to voltage, frequency, power
                                     Trip                                                               105
                                                           protections
                                     Min-Max-Med           History of minimum, maximum and mean voltages and
                                     measurements          powers recorded within a settable range      105
                                                           Real time measurement of the peak factor of the
                                     Peak factor                                                        105
                                                           currents
                                     Power factor          Real time measurement of the power factor    105
                                     Energy counters       Measurement of active, reactive, apparent energy  105

                                    The relative associated measurements are activated by means of the Ekip Synchrocheck module (page
                                    167).



        Instantaneous measurements Instantaneous currents, available in the Summary pages, are real time measurements of the line-to-line
                                    and phase voltages expressed in root-mean-square value.
                                    Representation, measuring range and performance depend on the set rated voltage (Un).
                                    Available in the Summary pages, the instantaneous powers are real time measurements of the phase and
                                    total active powers.
                                    Representation, measuring range and performance depend on the set rated voltage (Un) and on the rated
                                    current defined by the rated size of the Trip unit (In); in addition, the reference changes on the basis of
                                    the type of measurement:
                                     •  Sn for total powers (Sn = In * Un * √3).
                                     •  Pn for phase powers (Pn = In * Un / √3).
                                           NOTE: the phase powers and voltages are available with 4P and 3P + N CBs
                                                        Monitor time (min-  Normal operating   Accuracy of value
                                     Measurement
                                                        max)                range              read   (1)
                                     Line-to-line voltages  (6)  5 V ÷ 900 V  100 ÷ 690 V      0.5 %
                                     Phase voltages     5 V ÷ 900 V         50 ÷ 400 V         0.5 %
                                     Line frequency     30 ÷ 80 Hz   (2)    f -10 % ÷ f +10 %   (4)  0,1 %   (3)
                                     Total active, reactive        (5)                             (3)
                                     and apparent power  (7)  Pmin ÷ Pmax   0,3 ÷ 1,2 Sn       2 %
                                     Active, reactive and   Pmin ÷ Pmax  (5)  0,3 ÷ 1,2 Pn     2 %   (3)
                                     apparent phase power


                                    (1)  the accuracies refer to normal operating ranges, as established by IEC 61557-12
                                    (2)  available for voltage values of over 30 V (with Un < 277 V) or 60 V (with Un > 277 V)
                                    (3)  accuracies based on Ekip Touch and Ekip Touch Measuring without Class 1 Power & Energy
                                    Metering package; if the Class 1 Power & Energy Metering package is present and for all other trip
                                    unit models, check the indicated performance values from page 107
                                    (4)  45 to 55 Hz with set frequency = 50 Hz; 54 to 66 Hz with f = 60 Hz
                                    (5)  Pmin = 0,5 In x 5 V; Pmax= 3 x 16 In x 900 V
                                    (6)  the higher line-to-line voltages are also available in the Histograms, Measuring instruments and
                                    Measurement summary pages
                                    (7)  the higher total powers are also available in the Measuring instruments and Measurement
                                    summary pages

                                                                                                Continued on the next page








       104 | © 2022 ABB |  1SDH002039A1002 - ECN000212994              Ekip Touch - Measurements | 2 - Measuring Measurements
   101   102   103   104   105   106   107   108   109   110   111