Page 38 - MCCB-XT5
P. 38

ABB | SACE Tmax XT

                   Installation menu If Ekip Touch detects that Rating Plug or Measurement module have not been installed properly, it signals
                                    an alarm (page 19) and completes Settings menu with the specific installation section:
                                     Menu               Submenus 1          Submenus 2         Commands
                                                                            Rating Plug        Install
                                     Circuit Breaker    Installation
                                                                            Ekip Measuring     Install

                                    Correct installation is confirmed by a message on the display and disappearance of the alarm signal and
                                    installation menu.
                                           NOTE: availability of submenus depends on the module, which appears to have not been
                                           installed



                         Test Menu                                      Description, parameters and Com-
                                     Menu             Submenus                                            Page
                                                                        mands
                                     Autotest         -                 Autotest command                  124
                                     Trip Test        -                 TRIP command                      124
                                     Test CB          -                 Close CB, Open CB                 124
                                     Ekip CI  (5)     -                 Autotest command                  125
                                                      Ekip Signalling 2K-1  (1)
                                     Ekip Signalling 2K  (1)  Ekip Signalling 2K-2  (1)  Module autotest command  125
                                                      Ekip Signalling 2K-3  (1)
                                                      S Protection  (3)
                                     ZoneSelectivity  (2)               Input, Force Output, Release Output  125
                                                      G Protection  (4)

                                    (1)  available if one or more Ekip Signalling modules are connected and detected by Ekip Touch
                                    (2)  available if Ekip Touch is on with auxiliary supply
                                    (3)  available with S and/or S2 and/or D protection enabled, for S protection the set curve must be t=k
                                    (4)  available with G and/or D protection enabled and curve t=k
                                    (5)  available if the Ekip CI module is connected and detected by Ekip Touch

                        About Menu   Menu               Submenus            Information provided
                                                                            Information about Ekip Touch: Trip unit serial
                                     Protection Unit    -                   number, type, version, standard, SW version,
                                                                            date and time, language
                                                                            CB information: TAG name, CB name, rated
                                     Circuit Breaker    -                   current, number of poles, CB status and
                                                                            position, total operations, CB serial number
                                                                            Status of 1% measurements (from Class 1 Power
                                     IEC 61557-12  (1)  -                   & Energy Metering package), serial number of
                                                                            assembly and current sensors connected
                                     Feature Collection  -                  List of tripped protections in Trip unit
                                                                            Module information: serial number, SW version,
                                     Modules            Modul x  (2)
                                                                            status of inputs/outputs/contacts (if present)

                                    (1)  available if Class 1 Power & Energy Metering SW package is provided for by Trip unit module or if it
                                    has been previously activated
                                    (2)  available if one or more modules are connected and detected by unit






















       36 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                          Ekip Touch - Interface and menus | 4 - Menu
   33   34   35   36   37   38   39   40   41   42   43