Page 38 - MCCB-XT5
P. 38
ABB | SACE Tmax XT
Installation menu If Ekip Touch detects that Rating Plug or Measurement module have not been installed properly, it signals
an alarm (page 19) and completes Settings menu with the specific installation section:
Menu Submenus 1 Submenus 2 Commands
Rating Plug Install
Circuit Breaker Installation
Ekip Measuring Install
Correct installation is confirmed by a message on the display and disappearance of the alarm signal and
installation menu.
NOTE: availability of submenus depends on the module, which appears to have not been
installed
Test Menu Description, parameters and Com-
Menu Submenus Page
mands
Autotest - Autotest command 124
Trip Test - TRIP command 124
Test CB - Close CB, Open CB 124
Ekip CI (5) - Autotest command 125
Ekip Signalling 2K-1 (1)
Ekip Signalling 2K (1) Ekip Signalling 2K-2 (1) Module autotest command 125
Ekip Signalling 2K-3 (1)
S Protection (3)
ZoneSelectivity (2) Input, Force Output, Release Output 125
G Protection (4)
(1) available if one or more Ekip Signalling modules are connected and detected by Ekip Touch
(2) available if Ekip Touch is on with auxiliary supply
(3) available with S and/or S2 and/or D protection enabled, for S protection the set curve must be t=k
(4) available with G and/or D protection enabled and curve t=k
(5) available if the Ekip CI module is connected and detected by Ekip Touch
About Menu Menu Submenus Information provided
Information about Ekip Touch: Trip unit serial
Protection Unit - number, type, version, standard, SW version,
date and time, language
CB information: TAG name, CB name, rated
Circuit Breaker - current, number of poles, CB status and
position, total operations, CB serial number
Status of 1% measurements (from Class 1 Power
IEC 61557-12 (1) - & Energy Metering package), serial number of
assembly and current sensors connected
Feature Collection - List of tripped protections in Trip unit
Module information: serial number, SW version,
Modules Modul x (2)
status of inputs/outputs/contacts (if present)
(1) available if Class 1 Power & Energy Metering SW package is provided for by Trip unit module or if it
has been previously activated
(2) available if one or more modules are connected and detected by unit
36 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 Ekip Touch - Interface and menus | 4 - Menu