Page 42 - MCCB-XT5
P. 42

ABB | SACE Tmax XT
        Protections




       1 - Protections - Introduction



                 Operating principle The protection functions are available with all Ekip Touch models and versions.
                                    Each protection is associated with a different signal (current, voltages, frequencies, powers, etc) but the
                                    operating principle is the same:
                                      1.   If the signal measured exceeds the set threshold, the specific protection activates (prealarm and/
                                         or alarm).
                                      2.  The  alarm appears on the display and, after a period of time (timing t ), depending on the
                                                                                                   t
                                         protection parameters set, can convert into a trip command (TRIP) transmitted to the internal
                                         Trip coil of the CB.
                                           NOTE:
                                            •  if the signal measured drops below the set threshold before the trip time has elapsed, Ekip
                                              Touch quits the alarm and/or timing status and returns to the normal operating condition
                                            •  all protections have a default configuration: check the parameters and change to suit the
                                              installation requirements before putting into service


                              TRIP When the Ekip CI module is present, Ekip M Touch allows a different TRIP configuration to be selected so
                                    that, if a trip occurs, a contact of the Ekip CI module connected to an external remote control switch is
                                    commanded (Normal mode).
                                           NOTE: TRIP is always controlled by a command to the Trip Coil for protections I and G

                                    Consult the parameters used with Ekip Touch MLRIU for further details (page 121).


                         References Many of the protection thresholds are displayed in two different quantities: absolute value and relative
                                    value.
                                    The relative value depends on the type of measurement:
                                     Type of protection  Reference          Description
                                     Current            In                  Nominal current of the Rating plug
                                     Voltage            Un                  Line-to-line voltage setting
                                     Frequency          fn                  Frequency setting
                                     Power              Sn                  √3 x In x Un




               Protections packages The protections described in the following chapters are grouped into packages, the availability of which
                                    depends on the model and version of the Trip unit, and on their ability to be installed as additional
                                    package:

                                     Package                                Page
                                     Standard Protections                   41
                                     Voltage protections                    51
                                     Voltage Advanced protections           54
                                     Frequency protections                  58
                                     Power protections                      61
                                     ROCOF protections                      67
                                     Adaptive protections                   68
                                     Motor protections                      69
                                     Additional protections and functions   73











       40 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                           Protections | 1 - Protections - Introduction