Page 11 - dehn-catalogue-lightning-protection_3
P. 11

Requirements for External Lightning Protection Components



           Components used for installing the external lightning protection
           system shall meet the mechanical and electrical requirements,
           as specified in the EN 62561-x standard series. Lightning protec-
           tion components are categorised according to their function, for
           example  connection  components  (EN  62561-1),  conductors  and
           earth electrodes (EN 62561-2).
           Testing of conventional lightning protection components
           Metal lightning protection components (clamps, conductors, air-termina-
           tion rods, earth electrodes) exposed to the elements have to be subjected
           to artificial ageing/conditioning prior to testing to verify their suitability
           for the intended application. In accordance with EN 60068-2-52 and EN
           ISO 6988 metal components are subjected to artificial ageing and tested
           in two steps.                                                 Figure 1:
                                                                   Test in a salt mist
           Natural weathering of lightning protection components and     chamber.
           exposure to corrosion

           Step 1: Salt mist treatment
           This test applies to components or devices for installation in saline at-
           mospheres. The specimens are tested with severity level 2 in a salt mist
           chamber (Figure 1) for three days. Test level 2 consists of three spraying
           phases of 2 h each, using a 5% sodium chloride solution (NaCl) at tem-
           peratures between 15 °C and 35 °C followed by storage at a relative
                     +2
           humidity of 93  –3 % and a temperature of 40 ±2 °C for 20 to 22 hours in
           accordance with EN 60068-2-52.
           Step 2: Humid sulphurous atmosphere treatment
           This test is to evaluate the resistance of materials or objects to con-
           densed humidity containing sulphur dioxide in accordance with EN ISO
           6988.
           The test is carried out in a test chamber (Figure 2) in seven test cycles of
                                                           -6
           24 h each in a sulphur dioxide concentration of 667 x 10  (±24 x 10 )
                                                  -6
           of the volume. Each cycle has a heating period of 8 h at a temperature
           of 40 ±3 °C in a humid, saturated atmosphere followed by a rest peri-
           od of 16 h. After that, the humid sulphurous atmosphere is replaced.   Figure 2:
           Both components for outdoor use and components buried in the ground   Test in a Kesternich
           are subjected to ageing / conditioning. For components buried in the   chamber.
           ground additional requirements and measures have to be considered.
           No aluminium clamps or conductors may be buried in the ground. If
           stainless steel is to be buried in the ground, only high-alloy stainless
           steel  may  be  used,  e.g.  StSt  (V4A).  In  accordance  with  the  German
           DIN VDE 0151 standard, StSt (V2A) is not allowed. Components for indoor
           use such as equipotential bonding bars do not have to be subjected
           to ageing / conditioning. The same applies to components which are
           embedded in concrete. These components are therefore often made of
           non-galvanised (black) steel.

           Air-termination systems / air-termination rods
           Air-termination rods are typically used as air-termination systems. They
           are available in many different designs,  ranging from 1 m for installation
           with concrete base on flat roofs, to telescopic lightning protection masts
           with a length of 25 m for biogas plants.             material combinations are decisive in this respect. The kind of conductor
           EN 62561-2 specifies the minimum cross sections and the permissible   routing describes how a clamp connects the conductors in cross or par-
           materials with the corresponding electrical and mechanical properties for   allel arrangement.
           air-termination rods.                                In case of a lightning current load, clamps are subjected to electrody-
           In case of air-termination rods with larger heights, the bending resistance   namic and thermal forces which highly depend on the kind of conductor
           of the air-termination rod and the stability of complete systems (air-ter-  routing and the clamp connection. Table 1 shows materials which may
           mination rod in a tripod) have to be verified by means of a static calcu-  be combined without causing contact corrosion.
           lation. Selection of the required cross sections and materials is based   The combination of different materials with one another and their differ-
           on this calculation. The wind speeds of the relevant wind load zone also   ent mechanical strengths and thermal properties have different effects
           have to be taken into account for this calculation.  on  the  connection  components  when  lightning  current  flows  through
                                                                them. This  is  particularly  evident  for  stainless  steel  (StSt)  connection
           Testing of connection components                     components where high temperatures occur due to the low conductivity
           Connection components, often simply called clamps, are used as light-  as soon as lightning currents flow through them. Therefore, a lightning
           ning  protection  components  to  connect  conductors  (down  conductor,   current test in compliance with EN 62561-1 has to be carried out for all
           air-termination conductor, earth entry) to each other or to an installation.   clamps. In order to test the worst case, not only the different conductor
           Depending on the type of clamp and clamp material, a lot of different   combinations but also the material combinations specified by the manu-
           clamp combinations are possible. The conductor routing and the possible   facturer have to be tested.
                                                                                                                7
   6   7   8   9   10   11   12   13   14   15   16