Page 12 - dehn-catalogue-lightning-protection_3
P. 12

Requirements for External Lightning Protection Components



        Tests based on the example of an MV clamp            electrical test the specimens have to be fixed on an insulating plate
        At first, the number of test combinations has to be determined. The MV   (Figure 5).
        clamp used is made of stainless steel (StSt) and hence can be combined   Three lightning current impulses of 10/350 μs wave form with 50 kA (nor-
        with steel, aluminium, StSt and copper conductors as stated in Table 1.   mal duty) and 100 kA (heavy duty) are applied to every specimen. After
        Moreover, it can be connected in cross and parallel arrangement which   being loaded with lightning current, the specimens must not show signs
        also has to be tested. This means that there are eight possible test com-  of damage.
        binations for the MV clamp used (Figures 3 and 4).   In addition to the electrical tests where the specimen is subjected to elec-
                                                             trodynamic forces in case of a lightning current load, a static-mechanical
        In accordance with EN 62561 each of these test combinations has to   load was integrated in the EN 62561-1 standard. This static-mechanical
        be tested on three suitable specimens / test set-ups. This means that   test is particularly required for parallel connectors, longitudinal connec-
        24 specimens of this single MV clamp have to be tested to cover the   tors, etc. and is carried out with different conductor materials and clamp-
        complete range. Every single specimen is mounted with the adequate   ing  ranges. The  connection  components  are  prepared  with  a  defined
        tightening torque in compliance with normative requirements and is   tightening torque and then loaded with a mechanical tensile force of 900
        subjected to artificial ageing by means of salt mist and humid sulphur-  N (± 20 N) for one minute. During this test period, the conductors must
        ous  atmosphere  treatment  as  described  above.  For  the  subsequent   not  move  more  than  one  millimetre  and  the  connection  components
                                                                              must not show signs of damage. This additional
                                                                              static-mechanical test is another test criterion
                     Steel  Aluminium  Copper    StSt    Titanium   Tin       for connection components and also has to be
         Steel (St/tZn)  yes   yes       no       yes      yes      yes       documented in the manufacturer’s test report in
          Aluminium   yes      yes       no       yes      yes      yes       addition to the electrical values.
                                                                              The  contact  resistance  (measured  above  the
           Copper     no       no       yes       yes      no       yes       clamp)  for  a  stainless  steel  clamp  must  not
            StSt      yes      yes      yes       yes      yes      yes       exceed 3 mΩ or 1 mΩ in case of other mate-
          Titanium    yes      yes       no       yes      yes      yes       rials. The required loosening torque has to be
                                                                              ensured.  A  manufacturer’s  test  report  is  pre-
            Tin       yes      yes      yes       yes      yes      yes
                                                                              pared  for  every  test  combination.  A  detailed
        Table 1:  Possible material combinations for air-termination systems and down conductors and for   test report is available from the manufacturer
               connection with structural parts.                              upon request or a less detailed report can be
                                                                              downloaded  from  the  internet  (www.dehn-in-
                                                                              ternational.com => Product data).

                                                                                       Consequently, installers of light-
                                                                                       ning  protection  systems  have  to
                                                                                       select the connection components
                                                                                      for the duty (H or N) to be expected
                                                                                     on site. A clamp for duty H (100 kA), for
                                                                              example, has to be used for an air-termination
                                ▲ new components                              rod (full lightning current) and a clamp for duty N
                                ▼ aged components                             (50 kA) has to be used in a mesh or at an earth
                                                                              entry (lightning current already distributed).



                                                                              Conductors
                                                                              EN  62561-2  also  places  special  demands  on
                                                                              conductors  such  as  air-termination  and  down
                                                                              conductors or earth electrodes e.g. ring earth
                                                                              electrodes, for example:
        Figure 3:  New and aged components.
                                                                              •  Mechanical properties (minimum tensile
                                                                                strength, minimum elongation),
                                                                              •  Electrical properties (max. resistivity) and
                                                                              •  Corrosion resistance properties
                                                                                (artificial ageing as described above).


















        Figure 4:  Test combinations for MV clamps    Figure 5: Specimen fixed on insulating plate
               (parallel and cross arrangement).    (MV clamp) for a test in the
                                                   impulse current laboratory.
        8
   7   8   9   10   11   12   13   14   15   16   17