DEHNiso Spacers
If air-termination rods are fixed by means of spacers, the calculations are based on the installation possibilities below. The maximum per-
missible gust wind speeds are specified for the relevant products and have to be considered for selection / installation. A higher mechanical
strength can be achieved by means of e.g. an angled support (two spacers arranged in a triangle) (on request).
Installation Installation Installation
possibility 1 possibility 2 possibility 3
free length of max. 2.0 m free length of max. 2.0 m distance of max. 15 cm free length of max. 2.0 m
fixing length 0.5 – 1.0 m fixing length 0.5 – 1.0 m fixing length 0.5 – 1.0 m
Variable holders for conductors and air-termination rods for keeping the separation distance according to IEC/EN 62305-3.
Spacer bar made of glass-fibre reinforced plastic (GRP), Ø16 mm, UV-stabilised, light grey colour.
With rod holder and fixing plate 106 115 106 120 106 123 DIDH 16 530 BP V2A GFK
DIDH 16 690 BP V2A GFK
DIDH 16 1030 BP V2A GFK
Fixed conductor routing.
106 115 pc(s) 37,80 € 4013364100213 01 01 01 06 488 g 552 g 1 1
4013364092945 01 01 01 06
Part No. 106 115 106 120 106 123 pc(s) 41,61 € 4013364100220 01 01 01 06 686 g 1
106 120
106 123
pc(s) 51,29 €
Conductor support Rd 16 mm 16 mm 16 mm
Material of conductor holder StSt StSt StSt
Length 530 mm 690 mm 1030 mm
Insulating clearance 445 mm 605 mm 945 mm Eurocode
[8x] Ø5.1 / [4x] 7 x 10 [8x] Ø5.1 / [4x] 7 x 10 [8x] Ø5.1 / [4x] 7 x 10
Fixing
/ [2x] 11 x 20 mm / [2x] 11 x 20 mm / [2x] 11 x 20 mm
Permanent temperature range -50 °C ... +100 °C -50 °C ... +100 °C -50 °C ... +100 °C
Max. gust wind speed installation possibility 1 130 km/h 125 km/h 120 km/h
PU 1 pc(s) 1 pc(s) 1 pc(s)
With conductor holder and fixing plate 106 090 106 100 106 105 DIDH 7.10 530 BP V2A GFK
DIDH 7.10 690 BP V2A GFK
DIDH 7.10 1030 BP V2A GFK
Fixed conductor routing.
106 090 4013364100190 01 01 01 06 470 g 1
pc(s) 37,80 € 4013364092907 01 01 01 06 545 g 1
Part No. 106 090 106 100 106 105 106 105 pc(s) 51,71 € 4013364100206 01 01 01 06 658 g 1
106 100
pc(s) 42,64 €
Conductor support Rd 7-10 mm 7-10 mm 7-10 mm
Material of conductor holder StSt StSt StSt
Length 530 mm 690 mm 1030 mm
Insulating clearance 445 mm 605 mm 945 mm Eurocode
[8x] Ø5.1 / [4x] 7 x 10 [8x] Ø5.1 / [4x] 7 x 10 [8x] Ø5.1 / [4x] 7 x 10
Fixing
/ [2x] 11 x 20 mm / [2x] 11 x 20 mm / [2x] 11 x 20 mm
Permanent temperature range -50 °C ... +100 °C -50 °C ... +100 °C -50 °C ... +100 °C
Max. gust wind speed (holder distance 1000 mm, Al Ø8-10 mm) 224 km/h 184 km/h 137 km/h
PU 1 pc(s) 1 pc(s) 1 pc(s)
With rod holder and pipe clamp 106 225 106 226 106 228 DIDH 16 530 RS40.60 V2A
DIDH 16 690 RS40.60 V2A
DIDH 16 1030 RS40.60 V2A
Part No. 106 225 106 226 106 228
106 225 pc(s) 41,51 € 4013364100299 01 01 01 06 684 g 722 g 1 1
106 226
4013364098930 01 01 01 06
Conductor support Rd 16 mm 16 mm 16 mm pc(s) 45,11 € 4013364100305 01 01 01 06 878 g 1
106 228
pc(s) 56,14 €
Material of conductor holder StSt StSt StSt Isolated Lightning Protection
Length 530 mm 690 mm 1030 mm
Insulating clearance 445 mm 605 mm 945 mm Eurocode 9
Clamping range of pipe 40-60 mm (1 /4-2") 40-60 mm (1 /4-2") 40-60 mm (1 /4-2")
1
1
1
Permanent temperature range -50 °C ... +100 °C -50 °C ... +100 °C -50 °C ... +100 °C
Max. gust wind speed installation possibility 2 130 km/h 121 km/h 103 km/h
PU 1 pc(s) 1 pc(s) 1 pc(s)
Valid as of March 1, 2020 Detailed product information can be found on our website 115