Page 138 - dehn-catalogue-lightning-protection_3
P. 138

Reinforcement Technology


                         Connecting Clamps for Reinforcements
                         In accordance with the German standard DIN 18014: 2014-03 Fundamenterder – Planung, Ausführung und Dokumentation (Foundation
                         earth electrode - Planning, execution and documentation), foundation earth electrodes have to be connected with the reinforcement of the
                         foundation slab at intervals of 2 metres. Of the various connection possibilities, clamp connections have turned out to be the most economic
                         as they can be implemented quickly and easily on site.

                         According to the current lightning protection standards, reinforcing steels should, among other things, be used as natural components of the
                         down conductor system. The table below provides an overview of the nominal and outer diameters as well as cross sections of the reinforcing
                         steels DIN EN 10080: 2005.
                         For connecting reinforcing steel meshes or reinforcements with round and flat conductors.
                         Arrangement: (II) = parallel    (+) = cross


                                                 Nominal diameter d S        Outer diameter d A











                                             The outer diameter including corrugation is approx. d A = 1.15 x d S .

                               Nominal diameter d s (mm)  6  8  10  12   14    16   20    25    28   32    40
                             Average outer diameter incl.   7.1  9.4  11.8  14.2  16.5  18.9  23.6  29.5  33.1  37.8  47.2
                                   corrugation d A (mm)
                             Nominal cross section (mm 2 )  28.3  50.3  78.5  113.1  154  201  314  491  616  804  1257



                         DEHNclip Rebar Clamp

                         Quick and safe:
                         DEHNclip rebar clamp for quick connection of the earth electrode to the reinforcement without tools. DEHNclip is tested for a lightning current
                         carrying capability of 50 kA (10/350 µs) in accordance with EN 62561-1.

        308 130   DC BK 6 RD10 STBLANK
        308 131   DC BK 8 RD10 STBLANK
        308 132   DC BK 10 RD10 STBLANK  For connecting round conductors with the reinforcement
        308 133   DC BK 12 RD10 STBLANK
                          Part No.                    308 130       308 131       308 132       308 133
            308 130
                          Material                    St/bare       St/bare       St/bare       St/bare
                          Clamping range Rd* / Rd     6-7 / 10 mm   8-9 / 10 mm   10 / 10 mm    12 / 10 mm
        4013364288942  03 01 01 01   18 g   50   pc(s)   2,22
        €
        308 131   4013364288881  03 01 01 01   18 g   50
        pc(s)  2,22 €
        308 132   4013364288423  03 01 01 01   20 g   50
        pc(s)  2,22 €
        308 133   4013364288911  03 01 01 01   20 g   50
        pc(s)  2,22 €     Short-circuit current (50 Hz)  (1 s; ≤ 300 °C)  2.5 kA  2.7 kA  2.4 kA  2.7 kA
                          Standard                    EN 62561-1    EN 62561-1    EN 62561-1    EN 62561-1
                          PU                          50 pc(s)      50 pc(s)      50 pc(s)      50 pc(s)
                         *)  Nominal diameter ds of the reinforcement
        308 140   DC BK 6 FL30 STBLANK
        308 141   DC BK 8 FL30 STBLANK  For connecting flat conductors with the reinforcement
        308 142   DC BK 10 FL30 STBLANK
        308 143   DC BK 12 FL30 STBLANK
                          Part No.                    308 140       308 141       308 142       308 143
            308 140
                          Material                    St/bare       St/bare       St/bare       St/bare
        4013364288935  03 01 01 01   21 g   50   pc(s)   2,37
        €
        308 141   4013364288904  03 01 01 01   19 g   50
        pc(s)  2,37 €     Clamping range Rd* / Fl     6-7 / 30 mm   8-9 / 30 mm   10 / 30 mm    12 / 30 mm
        308 142   4013364288522  03 01 01 01   18 g   50
        pc(s)  2,37 €
        308 143   4013364289123  03 01 01 01   18 g   50
        pc(s)  2,37 €
                          Short-circuit current (50 Hz)  (1 s; ≤ 300 °C)  2.0 kA  2.3 kA  2.3 kA  2.3 kA
                          Standard                    EN 62561-1    EN 62561-1    EN 62561-1    EN 62561-1
                          PU                          50 pc(s)      50 pc(s)      50 pc(s)      50 pc(s)
                         *)  Nominal diameter ds of the reinforcement
        308 134   DC BK 6 RD6 STBLANK
        308 135   DC BK 8 RD8 STBLANK
        308 137   DC BK 8 RD12 STBLANK  For connecting reinforcing steel
        308 136   DC BK 12 RD12 STBLANK
                          Part No.                    308 134       308 135       308 137       308 136
            308 134
                          Material                    St/bare       St/bare       St/bare       St/bare
        4013364308091  03 01 01 01   18 g   50   pc(s)   2,22   Clamping range Rd* / Rd*  6-7 / 6-7 mm  8-9 / 8-9 mm  8-9 / 12 mm  12 / 12 mm
        €
        308 135   4013364308107  03 01 01 01   18 g   50
        pc(s)  2,22 €
        308 137   4013364308121  03 01 01 01   18 g   50
        pc(s)  2,22 €
        308 136   4013364308114  03 01 01 01   18 g   50
                          Short-circuit current (50 Hz)  (1 s; ≤ 300 °C)  2.2 kA  2.4 kA  2.4 kA  2.6 kA
        pc(s)  2,22 €
                          Standard                    EN 62561-1    EN 62561-1    EN 62561-1    EN 62561-1
                          PU                          50 pc(s)      50 pc(s)      50 pc(s)      50 pc(s)
                         *)  Nominal diameter ds of the reinforcement