In accordance with the German standard DIN 18014: 2014-03 Fundamenterder – Planung, Ausführung und Dokumentation (Foundation
earth electrode - Planning, execution and documentation), foundation earth electrodes have to be connected with the reinforcement of the
foundation slab at intervals of 2 metres. Of the various connection possibilities, clamp connections have turned out to be the most economic
as they can be implemented quickly and easily on site.
According to the current lightning protection standards, reinforcing steels should, among other things, be used as natural components of the
down conductor system. The table below provides an overview of the nominal and outer diameters as well as cross sections of the reinforcing
steels DIN EN 10080: 2005.
For connecting reinforcing steel meshes or reinforcements with round and flat conductors.
Arrangement: (II) = parallel (+) = cross
Nominal diameter d S Outer diameter d A
The outer diameter including corrugation is approx. d A = 1.15 x d S .
Nominal diameter d s (mm) 6 8 10 12 14 16 20 25 28 32 40
Average outer diameter incl. 7.1 9.4 11.8 14.2 16.5 18.9 23.6 29.5 33.1 37.8 47.2
corrugation d A (mm)
Nominal cross section (mm 2 ) 28.3 50.3 78.5 113.1 154 201 314 491 616 804 1257
DEHNclip Rebar Clamp
Quick and safe:
DEHNclip rebar clamp for quick connection of the earth electrode to the reinforcement without tools. DEHNclip is tested for a lightning current
carrying capability of 50 kA (10/350 µs) in accordance with EN 62561-1.
308 130 DC BK 6 RD10 STBLANK
308 131 DC BK 8 RD10 STBLANK
308 132 DC BK 10 RD10 STBLANK For connecting round conductors with the reinforcement
308 133 DC BK 12 RD10 STBLANK
Part No. 308 130 308 131 308 132 308 133
308 130
Material St/bare St/bare St/bare St/bare
Clamping range Rd* / Rd 6-7 / 10 mm 8-9 / 10 mm 10 / 10 mm 12 / 10 mm
4013364288942 03 01 01 01 18 g 50 pc(s) 2,22
€
308 131 4013364288881 03 01 01 01 18 g 50
pc(s) 2,22 €
308 132 4013364288423 03 01 01 01 20 g 50
pc(s) 2,22 €
308 133 4013364288911 03 01 01 01 20 g 50
pc(s) 2,22 € Short-circuit current (50 Hz) (1 s; ≤ 300 °C) 2.5 kA 2.7 kA 2.4 kA 2.7 kA
Standard EN 62561-1 EN 62561-1 EN 62561-1 EN 62561-1
PU 50 pc(s) 50 pc(s) 50 pc(s) 50 pc(s)
*) Nominal diameter ds of the reinforcement
308 140 DC BK 6 FL30 STBLANK
308 141 DC BK 8 FL30 STBLANK For connecting flat conductors with the reinforcement
308 142 DC BK 10 FL30 STBLANK
308 143 DC BK 12 FL30 STBLANK
Part No. 308 140 308 141 308 142 308 143
308 140
Material St/bare St/bare St/bare St/bare
4013364288935 03 01 01 01 21 g 50 pc(s) 2,37
€
308 141 4013364288904 03 01 01 01 19 g 50
pc(s) 2,37 € Clamping range Rd* / Fl 6-7 / 30 mm 8-9 / 30 mm 10 / 30 mm 12 / 30 mm
308 142 4013364288522 03 01 01 01 18 g 50
pc(s) 2,37 €
308 143 4013364289123 03 01 01 01 18 g 50
pc(s) 2,37 €
Short-circuit current (50 Hz) (1 s; ≤ 300 °C) 2.0 kA 2.3 kA 2.3 kA 2.3 kA
Standard EN 62561-1 EN 62561-1 EN 62561-1 EN 62561-1
PU 50 pc(s) 50 pc(s) 50 pc(s) 50 pc(s)
*) Nominal diameter ds of the reinforcement
308 134 DC BK 6 RD6 STBLANK
308 135 DC BK 8 RD8 STBLANK
308 137 DC BK 8 RD12 STBLANK For connecting reinforcing steel
308 136 DC BK 12 RD12 STBLANK
Part No. 308 134 308 135 308 137 308 136
308 134
Material St/bare St/bare St/bare St/bare
4013364308091 03 01 01 01 18 g 50 pc(s) 2,22 Clamping range Rd* / Rd* 6-7 / 6-7 mm 8-9 / 8-9 mm 8-9 / 12 mm 12 / 12 mm
€
308 135 4013364308107 03 01 01 01 18 g 50
pc(s) 2,22 €
308 137 4013364308121 03 01 01 01 18 g 50
pc(s) 2,22 €
308 136 4013364308114 03 01 01 01 18 g 50
Short-circuit current (50 Hz) (1 s; ≤ 300 °C) 2.2 kA 2.4 kA 2.4 kA 2.6 kA
pc(s) 2,22 €
Standard EN 62561-1 EN 62561-1 EN 62561-1 EN 62561-1
PU 50 pc(s) 50 pc(s) 50 pc(s) 50 pc(s)
*) Nominal diameter ds of the reinforcement
Reinforcement Technology
10 134 Detailed product information can be found on our website Valid as of March 1, 2020