Page 143 - dehn-catalogue-lightning-protection_3
P. 143

HVI Lightning Protection
                                                                                                                      HVI Lightning   Protection
















           High-voltage-resistant, insulated HVI Conductor:     The  application  range  was  gradually  expanded  to  include  HVI light,
           The innovation in external lightning protection      DEHNcon-H, HVI long, HVI power and HVI power long. As a result,
           In order to prevent dangerous flashover between components of the exter-  HVI Conductors can be used for an extremely wide range of applica-
           nal lightning protection system and conductive internal system components   tions.
           (electric lines, pipes, etc.) keeping the separation distance s is a crucial
           factor when designing and implementing a lightning protection system.  The separation distance is crucial
                                                                The  following  overview  makes  it  easier  to  select  the  right  HVI
           Unique design                                        Conductor. The criteria for this selection are the separation distance s
                                                                and the required class of LPS.
           When  using  conventional  lightning  protection  systems,  it  is  often  not
           possible to maintain the necessary separation distances. This is no prob-  The IEC 62305-3 standard requires that a defined separation distance
           lem with the HVI Conductor thanks to its unique design and special   be kept as a minimum distance between the lightning protection system
           sheath. The lightning current carrying conductor of the HVI Conductor   and electrically conductive materials. This prevents dangerous flashover
           is  wrapped  with  insulating  material  in  such  a  way  that  the  required   and thus sparking, ensuring that lightning currents are reliably conduct-
           separation distance from other conductive parts of the building, electric   ed to the earth-termination system. The high-voltage-resistant, insulated
           lines and pipes is maintained. The conductor consists of an inner copper   down conductors from DEHN provide an equivalent separation distance
           conductor  with  a  high-voltage-resistant  thick-walled  insulation  and  a   and thus meet the normative requirements.
           weather-resistant semi-conductive special outer sheath.
                                                                The separation distance can be calculated automatically by means
           Function of the HVI Conductor                        of the DEHNsupport Toolbox software.
           High impulse voltages cause flashover on the surface of insulating mate-
           rial if no additional measures are taken. This effect is also referred to as   Types of HVI Conductor
           creeping flashover. If the creeping discharge inception voltage is exceed-  Three types of HVI Conductor are available:
           ed, a surface discharge is initiated which can easily flash over a distance   •  HVI light, DEHNcon-H
           of several meters. To prevent creeping discharges, the HVI Conductor   •  HVI Conductor, HVI long Conductor
           features  a  special  outer  sheath  which  makes  it  possible  to  discharge   •  HVI power, HVI power long Conductor
           high lightning impulse voltages to a reference potential. For functional
           reasons, a connection is established between the semi-conductive outer
           sheath and the equipotential bonding system of the building (no light-  Each type of HVI Conductor has different strengths and characteristics
           ning voltage) in the sealing end range. This connection to the equipoten-  and  therefore  also  different  installation  requirements.  There  are  also
           tial bonding system can be made, e.g. on earthed metal roof-mounted   black and grey conductors within the HVI Conductor product line. The
           structures located in the protected zone of the lightning protection   additional grey sheath allows the HVI Conductor to be installed unob-
           system, earthed parts of the building structure that do not carry lightning   trusively on buildings.
           voltage or the protective conductor of the low-voltage system.
                                                                HVI Conductor inside the supporting tube –
           Types of HVI Conductor                               dimensioned according to Eurocode
           In 2003, DEHN launched an innovation in external lightning protection,   Both the material of the supporting tube and sufficient stability are cru-
           the high-voltage-resistant, insulated HVI Conductor. Since then, thou-  cial factors when choosing self-supporting air-termination systems with
           sands  of  buildings  and  installations  have  been  successfully  equipped   HVI Conductors installed inside / outside the supporting tube. The area
           with HVI Lightning Protection. The large number of HVI Conductors   exposed to wind is larger when HVI Conductors are installed outside
           installed  and  intensive  development  work  have  given  us  the  edge  in   the supporting tube. The standing surface and the necessary base weight
           terms of experience. This is reflected in the variety of HVI Conductors.   have to be considered accordingly.
           These meet the differing requirements on lightning protection systems.
                                                                The gust wind speed is determined using the following parameters:
                                                                •  Wind zone (I-V)
                                                                •  Terrain category
                                           Separation distance 90 cm  •  Object height
                                                      Class of LPS I – IV  •  Height of location above sea level
                                            HVI   power  HVI   power   long  (standard up to 800 m above sea level)

            Separation distance 75 cm                 200 kA    The table lists the respective maximum gust wind speeds for self-sup-
                            DEHNcon-H  HVI   long               porting air-termination systems with HVI Conductors. They have to be be
                                                      Class of LPS II – IV
                                                                compared with the defined values in the gust wind speeds table. If the

                        Separation distance 45 cm     150 kA    max. gust wind speed for an air-termination system is lower than the
                                                      Class of LPS II – IV  respective local gust wind speed, the air-termination system is suitable
                                                                for this application.
             HVI   black  HVI   grey  HVI   light  DEHNcon-H  150 kA  If necessary, permissible roof loads must be observed and coordinated with
                                                                the constructor.
           2003  2004  2007  2008   2011  2013  2015
           Valid as of March 1, 2020                                                                          139
   138   139   140   141   142   143   144   145   146   147   148