Page 163 - dehn-catalogue-lightning-protection_3
P. 163

DEHNcon-H


            3  Air-termination Mast for Sub-roof Installation of the HVI light Conductor
           For installation on the mounting bracket for installation on rafters.
           Optically optimised design because the HVI light Conductor is installed inside the supporting tube. The HVI light Conductor is led through the
           supporting tube of the mounting bracket for installation on rafters and installed in the area of the counter-battens / roof battens.
           Advantages:
           •  Sub-roof installation – invisible
           •  Only the supporting tube is visible
           •  No mechanical load, e.g. snow

           DEHNcon-H / HVI light Conductor inside the supporting tube with air-termination tip              819 243   HVI LI 20 L6M SR2875 FSP1000 DSH GFK AL
           With internal sealing end and air-termination tip Ø10 mm.
           PU 1 is the minimum order length of 6 m.                                                         819 243  pc(s)  700,40 €  4013364255951  01 07 01 02   7.93 kg  1
           Conductor length to be indicated when ordering (in steps of 0.5 m).                                        DEHNcon-H
           Part No.                    819 243
           Material of supporting tube  GRP / Al
           Length of supporting tube   2875 mm                                                     Eurocode
           Length of air-termination tip  1000 mm
           Outside diameter Ø GRP      30 mm
           Diameter Ø of conductor     20 mm
           Colour of conductor         grey 1
           Material of conductor       Cu
           Equivalent separation distance s (in air)  ≤ 45 cm
           Minimum order length        6 m
           Max. gust wind speed        160 km/h
           PU                          1 pc(s)





           DEHNcon-H Supporting Tube for HVI light Conductor, Sub-roof Installation

           Supporting tube for HVI light Conductor for on-site assembly, air-termination tip, StSt, Ø10 mm.
           With air-termination tip                                                                         105 288   SR D30 2875 FSP10 1000 DSH GFK AL V2A
           Part No.                    105 288
                                                                                                            105 288  pc(s)  320,33 €  4013364256040  01 07 01 01   4.55 kg  1
           Material of supporting tube  GRP / Al
           Length of supporting tube   2875 mm
           Length of air-termination tip  1000 mm
           Outside diameter Ø GRP      30 mm                                                       Eurocode
           Max. gust wind speed        160 km/h
           PU                          1 pc(s)










           HVI light Conductor
           System for keeping the separation distance, e.g. on flat roofs. The high-voltage-resistant, insulated HVI light Conductor prevents uncontrolled
           flashover to metal or electric components underneath the roofing.
           For use up to an equivalent separation distance s ≤ 45 cm (in air) or s ≤ 90 cm (solid material).

           HVI light Conductor (cut to length)                                                              819 129   HVI LI 45 20 L .. GR
           The cut-to-length HVI light Conductor is supplied in a cardboard box (max. 70 m).
           Conductor length has to be stated when ordering (in steps of 0.5 m).                             819 129  pc(s)  283,25 €  4013364223158  01 07 01 02   3.16 kg  1
           Part No.                    819 129
           Material of conductor       Cu
           Material of insulation      PE
           Material of sheath          PVC
           Colour of conductor         dark grey 1
           Colour RAL                  similar to 7000
           Cross-section of core       19 mm 2
           Equivalent separation distance s (in air)  ≤ 45 cm
           Diameter Ø conductor        20 mm
           Characteristics of sheath   UV-stabilised and weather-resistant
           Minimum order length        6 m
           PU                          1 pc(s)


           Valid as of March 1, 2020                        Detailed product information can be found on our website   159
   158   159   160   161   162   163   164   165   166   167   168