Page 163 - dehn-catalogue-lightning-protection_3
P. 163
DEHNcon-H
3 Air-termination Mast for Sub-roof Installation of the HVI light Conductor
For installation on the mounting bracket for installation on rafters.
Optically optimised design because the HVI light Conductor is installed inside the supporting tube. The HVI light Conductor is led through the
supporting tube of the mounting bracket for installation on rafters and installed in the area of the counter-battens / roof battens.
Advantages:
• Sub-roof installation – invisible
• Only the supporting tube is visible
• No mechanical load, e.g. snow
DEHNcon-H / HVI light Conductor inside the supporting tube with air-termination tip 819 243 HVI LI 20 L6M SR2875 FSP1000 DSH GFK AL
With internal sealing end and air-termination tip Ø10 mm.
PU 1 is the minimum order length of 6 m. 819 243 pc(s) 700,40 € 4013364255951 01 07 01 02 7.93 kg 1
Conductor length to be indicated when ordering (in steps of 0.5 m). DEHNcon-H
Part No. 819 243
Material of supporting tube GRP / Al
Length of supporting tube 2875 mm Eurocode
Length of air-termination tip 1000 mm
Outside diameter Ø GRP 30 mm
Diameter Ø of conductor 20 mm
Colour of conductor grey 1
Material of conductor Cu
Equivalent separation distance s (in air) ≤ 45 cm
Minimum order length 6 m
Max. gust wind speed 160 km/h
PU 1 pc(s)
DEHNcon-H Supporting Tube for HVI light Conductor, Sub-roof Installation
Supporting tube for HVI light Conductor for on-site assembly, air-termination tip, StSt, Ø10 mm.
With air-termination tip 105 288 SR D30 2875 FSP10 1000 DSH GFK AL V2A
Part No. 105 288
105 288 pc(s) 320,33 € 4013364256040 01 07 01 01 4.55 kg 1
Material of supporting tube GRP / Al
Length of supporting tube 2875 mm
Length of air-termination tip 1000 mm
Outside diameter Ø GRP 30 mm Eurocode
Max. gust wind speed 160 km/h
PU 1 pc(s)
HVI light Conductor
System for keeping the separation distance, e.g. on flat roofs. The high-voltage-resistant, insulated HVI light Conductor prevents uncontrolled
flashover to metal or electric components underneath the roofing.
For use up to an equivalent separation distance s ≤ 45 cm (in air) or s ≤ 90 cm (solid material).
HVI light Conductor (cut to length) 819 129 HVI LI 45 20 L .. GR
The cut-to-length HVI light Conductor is supplied in a cardboard box (max. 70 m).
Conductor length has to be stated when ordering (in steps of 0.5 m). 819 129 pc(s) 283,25 € 4013364223158 01 07 01 02 3.16 kg 1
Part No. 819 129
Material of conductor Cu
Material of insulation PE
Material of sheath PVC
Colour of conductor dark grey 1
Colour RAL similar to 7000
Cross-section of core 19 mm 2
Equivalent separation distance s (in air) ≤ 45 cm
Diameter Ø conductor 20 mm
Characteristics of sheath UV-stabilised and weather-resistant
Minimum order length 6 m
PU 1 pc(s)
Valid as of March 1, 2020 Detailed product information can be found on our website 159