Page 160 - dehn-catalogue-lightning-protection_3
P. 160
DEHNcon-H
1 2 DEHNcon-H
Isolated air-termination system for transmitters/receivers (parabolic, terrestrial antennas) or whole buildings or parts of a building.
Optically optimised design since the HVI light Conductor is installed inside the supporting tube, reduced dimensions of the supporting tubes
(Al tube 40 x 5 mm / GRP tube 30 x 3 mm) and low weight of the whole structure, also suitable for retrofitting on existing antenna poles.
Special internal sealing end with a flexible StSt strip is led out at the bottom end of the supporting tube for connection to the equipotential
bonding system.
819 255 HVI LI 20 L6M SR1990 FSP500 GFK AL V2A
819 256 HVI LI 20 L6M SR1990 FSP1000 GFK AL V2A
819 257 HVI LI 20 L6M SR2640 FSP500 GFK AL V2A HVI light Conductor inside the supporting tube with air-termination tip
819 258 HVI LI 20 L6M SR2640 FSP1000 GFK AL V2A
819 259 HVI LI 20 L7.5M SR5040 FSP500 GFK AL V2A
With internal sealing end and air-termination tip StSt Ø10 mm.
819 255 4013364255371 01 07 01 02 5.68 kg 1
pc(s) 562,38 €
819 256 4013364255388 01 07 01 02 6.03 kg 1
pc(s) 571,65 €
819 257 pc(s) 589,16 € 4013364255395 01 07 01 02 6.58 kg 1 General technical data:
6.97 kg 1
DEHNcon-H Material of supporting tube GRP / Al
819 258
4013364255418 01 07 01 02
pc(s) 597,40 €
4013364256088 01 07 01 02
10.99 kg 1
819 259
pc(s) 989,83 €
Material of conductor
Cu
Equivalent separation distance s (air) ≤ 45 cm
Min. clamping length 600 mm
Part No. 819 255 819 256 819 257
Eurocode
Length of supporting tube 1990 mm 1990 mm 2640 mm
Length of air-termination tip 500 mm 1000 mm 500 mm
Minimum order length 6 m 6 m 6 m
Max. gust wind speed 232 km/h 198 km/h 232 km/h
Max. free length 1890 mm 2390 mm 2540 mm
PU 1 pc(s) 1 pc(s) 1 pc(s)
Part No. 819 258 819 259
Length of supporting tube 2640 mm 5040 mm
Length of air-termination tip 1000 mm 500 mm
Minimum order length 6 m 7.5 m
Max. gust wind speed 198 km/h 148 km/h
Max. free length 3040 mm 4940 mm
PU 1 pc(s) 1 pc(s)
1 HVI light Conductor
System for maintaining the separation distance, e.g. on flat roofs. The high-voltage-resistant, insulated HVI light Conductor prevents uncon-
trolled flashover to metal or electric components underneath the roofing.
For use up to an equivalent separation distance s ≤ 45 cm (in air) or s ≤ 90 cm (solid material).
HVI light Conductor (on a reel)
819 125 HVI LI 45 20 L100M GR
The HVI light Conductor comes in a length of 100 m on a disposable plywood reel (diameter approx. 800 mm, width approx. 485 mm). Allen
819 125 4013364118416 01 07 01 02 520.00 g/m
100 m 41,72 € key included in delivery.
Part No. 819 125
Material of conductor Cu
Material of insulation PE
Material of sheath PVC
Colour of conductor dark grey 1
Cross section of core 19 mm 2
Diameter Ø conductor 20 mm
PU 100 m
HVI light Conductor (500 m on a reel)
819 124 HVI LI 45 20 L500M GR
HVI light Conductor comes in a length of 500 m on a disposable plywood reel (diameter approx. 1 m, width approx. 670 mm). Allen key
included in delivery. Total weight approx. 290 kg.
819 124
4013364329003 01 07 01 02 520.00 g/m 500 m
38,60 €
Part No. 819 124 +
Material of conductor Cu
Material of insulation PE
Material of sheath PVC
Colour of conductor dark grey 1
Cross section of core 19 mm 2
Diameter Ø conductor 20 mm
PU 500 m
156 Detailed product information can be found on our website Valid as of March 1, 2020