HVI Conductor

        The HVI / HVI long Conductor can be used for a wide range of installa-
        tions for example, to protect larger roof-mounted structures, antennas as                       s s
        well as masts with information technology systems against direct light-
        ning strikes. Due to its special characteristics, this conductor can also be                 ≤ 75 cm
        directly routed to the earth-termination system. If this is not required,                    < 75 cm
        connection to already existing conventional lightning protection systems
        (elevated / isolated ring conductor) is also possible.
        If power needs to be distributed to several conductors to reduce the sep-
        aration distance or if longer conductors are needed up to four additional
        conductors can be installed on the outside of the supporting tube using
        a special fixing kit.
    HVI   Conductor  With  the high-voltage-resistant, insulated  conductor  a separation  dis-
        tance to electrically conductive parts according to IEC 62305-3 is main-
        tained. Equivalent separation distance s ≤ 0.75 m (air) or s ≤ 1.5 m (solid
        material).
        Two versions are available depending on the application:
        •  HVI Conductor (pre-assembled)
        •  HVI long Conductor (on a reel / cut to length)


        HVI Conductor (pre-assembled)
        The pre-assembled HVI Conductors, both for installation inside and out-
        side the tube, have a tightly mounted head piece with a heat-shrinkable
        sleeve. The second conductor end can be precisely positioned with the
        connection element included as a loose part to suit the structure of the
        system.


        HVI long Conductor (on a plywood reel / cut to length)
        The HVI long Conductor can be assembled on site and thus allows for
        great flexibility when it comes to unknown or changing building situ-
        ations and structures (new buildings, restoration) where the exact HVI
        Conductor lengths of the lightning protection system cannot be deter-
        mined at the planning stage.
        The HVI long Conductor is available with a length of 100 m on a dispos-
        able plywood reel (diameter approx. 900 mm, width approx. 485 mm) or
        as cut to length version (6 - 70 m).
        The installer determines the exact length on site, cuts the conductor to
        length, strips it and attaches the sealing ends.




        Technical data                     HVI Conductor         HVI long Conductor     HVI long Conductor
                                           (pre-assembled)       (on a plywood reel)    (cut to length)
        Structure                          solid / stranded      solid / stranded       solid / stranded
        Cross-section of inner conductor (Cu)  19 mm 2           19 mm 2                19 mm 2
        Conductor colour                   black / grey          black / grey           black / grey
        Outer diameter                     20 / 23 mm            20 / 23 mm             20 / 23 mm
        Equivalent separation distance (air)  ≤ 75 cm            ≤ 75 cm                ≤ 75 cm
        Equivalent separation distance (solid material)  ≤ 150 cm  ≤ 150 cm             ≤ 150 cm
        Minimum bending radius (OD = outer diameter)  10 x OD, 200 / 230 mm  10 x OD, 200 / 230 mm  10 x OD, 200 / 230 mm
        Operating temperature              -30 °C ... +70 °C     -30 °C ... +70 °C      -30 °C ... +70 °C
        Temperature for installation       -5 °C ... +40 °C      -5 °C ... +40 °C       -5 °C ... +40 °C
        Tensile strength                   950 N                 950 N                  950 N
        UV stability / weather resistance  yes                   yes                    yes
        Tested with limp (10/350 µs) based on EN 62561-1  150 kA  150 kA                150 kA
        For use in class of LPS in case of a single down conductor
        without current distribution (kc = 1)  II, III, IV       II, III, IV            II, III, IV
        Installation in Ex zone 1 and 21   allowed               allowed                allowed
        Minimum order quantity             ≥ 6 m                 100 m                  ≥ 6 m
        Max. order length                  70 / 60 m               —                    70 / 60 m
        Cable weight  / 100 m              —                     48 / ~ 63 kg           —