HVI Conductor
The HVI / HVI long Conductor can be used for a wide range of installa-
tions for example, to protect larger roof-mounted structures, antennas as s s
well as masts with information technology systems against direct light-
ning strikes. Due to its special characteristics, this conductor can also be ≤ 75 cm
directly routed to the earth-termination system. If this is not required, < 75 cm
connection to already existing conventional lightning protection systems
(elevated / isolated ring conductor) is also possible.
If power needs to be distributed to several conductors to reduce the sep-
aration distance or if longer conductors are needed up to four additional
conductors can be installed on the outside of the supporting tube using
a special fixing kit.
HVI Conductor With the high-voltage-resistant, insulated conductor a separation dis-
tance to electrically conductive parts according to IEC 62305-3 is main-
tained. Equivalent separation distance s ≤ 0.75 m (air) or s ≤ 1.5 m (solid
material).
Two versions are available depending on the application:
• HVI Conductor (pre-assembled)
• HVI long Conductor (on a reel / cut to length)
HVI Conductor (pre-assembled)
The pre-assembled HVI Conductors, both for installation inside and out-
side the tube, have a tightly mounted head piece with a heat-shrinkable
sleeve. The second conductor end can be precisely positioned with the
connection element included as a loose part to suit the structure of the
system.
HVI long Conductor (on a plywood reel / cut to length)
The HVI long Conductor can be assembled on site and thus allows for
great flexibility when it comes to unknown or changing building situ-
ations and structures (new buildings, restoration) where the exact HVI
Conductor lengths of the lightning protection system cannot be deter-
mined at the planning stage.
The HVI long Conductor is available with a length of 100 m on a dispos-
able plywood reel (diameter approx. 900 mm, width approx. 485 mm) or
as cut to length version (6 - 70 m).
The installer determines the exact length on site, cuts the conductor to
length, strips it and attaches the sealing ends.
Technical data HVI Conductor HVI long Conductor HVI long Conductor
(pre-assembled) (on a plywood reel) (cut to length)
Structure solid / stranded solid / stranded solid / stranded
Cross-section of inner conductor (Cu) 19 mm 2 19 mm 2 19 mm 2
Conductor colour black / grey black / grey black / grey
Outer diameter 20 / 23 mm 20 / 23 mm 20 / 23 mm
Equivalent separation distance (air) ≤ 75 cm ≤ 75 cm ≤ 75 cm
Equivalent separation distance (solid material) ≤ 150 cm ≤ 150 cm ≤ 150 cm
Minimum bending radius (OD = outer diameter) 10 x OD, 200 / 230 mm 10 x OD, 200 / 230 mm 10 x OD, 200 / 230 mm
Operating temperature -30 °C ... +70 °C -30 °C ... +70 °C -30 °C ... +70 °C
Temperature for installation -5 °C ... +40 °C -5 °C ... +40 °C -5 °C ... +40 °C
Tensile strength 950 N 950 N 950 N
UV stability / weather resistance yes yes yes
Tested with limp (10/350 µs) based on EN 62561-1 150 kA 150 kA 150 kA
For use in class of LPS in case of a single down conductor
without current distribution (kc = 1) II, III, IV II, III, IV II, III, IV
Installation in Ex zone 1 and 21 allowed allowed allowed
Minimum order quantity ≥ 6 m 100 m ≥ 6 m
Max. order length 70 / 60 m — 70 / 60 m
Cable weight / 100 m — 48 / ~ 63 kg —