HVI Conductor
1 Supporting Tube with HVI Conductor
Optically optimised installation of the HVI Conductor inside the supporting tube creates less wind exposed area.
For use up to an equivalent separation distance s ≤ 75 cm (in air) or s ≤ 150 cm (solid material).
Conductor length to be indicated when ordering (steps of 0.5 m).
HVI Conductor in supporting tube with air-termination tip
819 326 HVI 20 M L6M SR3200 IP FSP1000 GFK AL
819 336 HVI 23 L6M SR3200 IP FSP1000 GFK AL
With internal sealing end and air-termination tip, StSt, Ø10 mm, length 1000 mm.
819 326 4013364260511 01 07 01 01 8.40 kg 1 pc(s)
827,09 € 819 336 Eurocode 9.60 kg 1 pc(s)
4013364241237 01 07 01 01
Part No. 819 326 819 336
861,08 €
Material of supporting tube GRP / Al GRP / Al
Length of supporting tube 3200 mm 3200 mm
Transport length 3200 mm 3200 mm
Outside diameter Ø 50 mm 50 mm
Diameter Ø conductor 20 mm 23 mm
Colour of conductor black 1 grey 1
Material of conductor Cu Cu
Minimum order length 6 m 6 m
Max. free length with air-termination tip (wall mounting) 3500 mm 3500 mm
Max. gust wind speed (wall mounting, 1x HVI inside)
237 km/h
237 km/h
HVI Conductor Max. gust wind speed (wall mounting, 1x HVI outside) 227 km/h 225 km/h
197 km/h
197 km/h
Max. gust wind speed (wall mounting, 4x HVI outside)
PU
Max. gust wind speed (tripod with supporting tube) see table on page 140. 1 pc(s) 1 pc(s)
819 328 HVI 20 M L6M SR3200 IP RFS2500 GFK AL
819 338 HVI 23 L6M SR3200 IP RFS2500 GFK AL
819 426 HVI 20 M L6M SR4700 IP RFS2500 GFK AL HVI Conductor in supporting tube with air-termination rod
819 438 HVI 23 L6M SR4700 IP RFS2500 GFK AL
With internal sealing end and air-termination rod, Al, Ø22 /16 / 10 mm, length 2500 mm.
819 328 4013364260504 01 07 01 01 8.80 kg 1 pc(s)
868,29 €
819 338 4013364241244 01 07 01 01 10.00 kg 1 pc(s)
902,28 €
819 426 4013364260474 01 07 01 01 11.30 kg 1 pc(s)
942,45 €
819 438 4013364241251 01 07 01 01 12.50 kg 1 pc(s) Part No. 819 328 819 338 819 426 819 438
976,44 €
Material of supporting tube GRP / Al GRP / Al GRP / Al GRP / Al
Eurocode
Length of supporting tube 3200 mm 3200 mm 4700 mm 4700 mm
Transport length 3200 mm 3200 mm 4700 mm 4700 mm
Outside diameter Ø 50 mm 50 mm 50 mm 50 mm
Diameter Ø conductor 20 mm 23 mm 20 mm 23 mm
Colour of conductor black 1 grey 1 black 1 grey 1
Material of conductor Cu Cu Cu Cu
Minimum order length 6 m 6 m 6 m 6 m
Max. free length with air-termination rod
(wall mounting) 5000 mm 5000 mm 5000 mm 5000 mm
Max. gust wind speed
(wall mounting, 1x HVI inside) 190 km/h 190 km/h 190 km/h 190 km/h
Max. gust wind speed
(wall mounting, 1x HVI outside) 175 km/h 175 km/h 175 km/h 175 km/h
Max. gust wind speed 163 km/h 163 km/h 163 km/h 163 km/h
(wall mounting, 4x HVI outside)
PU 1 pc(s) 1 pc(s) 1 pc(s) 1 pc(s)
Max. gust wind speed (tripod with supporting tube) see table on page 140.
HVI Conductor in supporting tube (side outlet) with air-termination tip and small tripod
819 371 HVI 20M L6M SR3200 SA FSP1000 AL DBS V2A
819 381 HVI 23 L6M SR3200 SA FSP1000 AL DBS V2A
With internal sealing end and air-termination tip, StSt, Ø10 mm, length 1000 mm.
819 371 4013364260498 01 07 01 01 17.00 kg 1
pc(s) 1.490,26 € With tripod (Part No. 105 390) and set of threaded rods (Part No. 105 397).
819 381 4013364241954 01 07 01 01 18.50 kg 1
pc(s) 1.524,25 €
Part No. 819 371 819 381
Material of supporting tube GRP / Al GRP / Al
Eurocode
Length of supporting tube 3200 mm 3200 mm
Transport length 3200 mm 3200 mm
Outside diameter Ø 50 mm 50 mm
Diameter Ø conductor 20 mm 23 mm
Colour of conductor black 1 grey 1
Material of conductor Cu Cu
Radius of tripod 600 mm 600 mm
Space required for tripod 1400 x 1200 mm 1400 x 1200 mm
Length of threaded rods M16 x 520 mm M16 x 520 mm
Minimum order length 6 m 6 m
PU 1 pc(s) 1 pc(s)
Max. gust wind speed (tripod with supporting tube) see table on page 140.
170 Detailed product information can be found on our website Valid as of March 1, 2020