Page 11 - dehn-catalogue-safety-equipment_0
P. 11

IS Insulating Sticks  SCS Switching Sticks  RST Rescue Rods  SZ Fuse Tongs  Inspection Camera  Ice Removal Rod  Insulating Stick with Crank Handle  Insulating Stick Kit
             ork accor
           1. Disconnect completely – Operating Sticks, Inspection Camera
           W
                      ding to the Five Safety Rules
           1. Disconnect completely – Operating Sticks, Inspection Camera

           Product                Type          Nominal voltage UN / Frequency fN Application                Page      Inspection Camera
           IS Insulating Sticks                                                                                       1.  Operating Sticks,
                                  IS Insulating   up to 123 kV / 50 Hz  For use in indoor and outdoor installations  10
                                  Sticks                                Screw-on switching stick head allows for use as
                                                                        switching stick
                                                                        Supporting head for hexagon shaft or T pin shaft
                                                                        For use as earthing stick
                                                                        For use as operating stick for insulating protective
                                                                        shutters

           SCS Switching Sticks
                                  SCS Switching   up to 123 kV / 50 Hz  For indoor and outdoor installations  13
                                  Sticks                                Fully insulated, massive switching stick head
                                                                        Allows a deep and safe reach into the installation
                                                                        For use as operating stick for insulating protective
                                                                        shutters

           RST Rescue Rods
                                  RST Rescue Rods up to 36 kV / 50 Hz   For use in indoor and outdoor installations  14
                                                                        Fully insulated and fixed rescue hook
                                                                        For rescuing persons from the live working zone in
                                                                        the event of an electrical accident

           SZ Fuse Tongs
                                  SZ Fuse Tongs  up to 36 kV / 50 Hz    Operating head with two adjustable jaws  14
                                                                        Straight or 20° angled operating head
                                                                        Secure clamping
                                                                        Wide clamping range from Ø30 to 90 mm

           Wireless Inspection Camera
                                  Wireless      up to 123 kV / 15 ... 60 Hz  Periodic visual inspection and documentation of   16
                                  Inspection                            electrical installations and equipment (also without
                                  Camera                                special training)
                                                                        Wireless WiFi camera operation via smartphon/tablet
                                                                        No downtimes due to disconnection of the installation

           Ice Removal Rod
                                  Ice Removal Rod up to 15 kV / 16.5 Hz and    For removing icicles in the vicinity of live parts  18
                                                25 kV / 50 Hz           Massive icicle removal hammer
                                                                        With telescopic handle


           Insulating Stick with Crank Handle
                                  Insulating Stick  up to 36 kV         For emergency operating of engine drives  19
                                                                        For indoor and outdoor installations


           Insulating Stick Kit for Cleaning the Windscreens of E-Locomotives
                                  Insulating Stick   up to 7.5 kV / d.c. and 25 kV / a.c. Insulating stick kit for cleaning the windscreens of   20
                                  Kit                                   electric locomotives


           Storage Bags and Transport Cases
                                                                                                              158
                                  Cases: Sheet steel or plastic
                                  Bags: Artificial leather or canvas

           Maintenance Tests according to German regulations DGUV Vorschrift 3 (former BGV A3)
                                  According to German regulations DGUV Vorschrift 3 (former BGV A3), operating sticks have to be tested for    145
                                  compliance with the prescribed limits as stated in the Electrical Safety Rules. This test is performed in the
                                  high-voltage test laboratory of DEHN and includes
                   2025           – measurement of the leakage current,
                                  – test for protection against bridging,
                 Wiederholungsprüfung
                   Nächste
                                  – visual inspection, manual tests and measurements.
                                  This maintenance test is documented in a test report and on the device.
                                  Prior to each use, operating sticks must be visually inspected for signs of damage or any other defect.
           Valid as of January 1, 2019                       You will find detailed product information on our website   9
   6   7   8   9   10   11   12   13   14   15   16