Service and Safety


        Maintenance test criteria for protective and auxiliary equipment
                       DGUV regulation 3 (former BGV A3)  VDE 0105-100  Equipment standard
        Earthing and   § 5 (1) [… It shall be checked whether   5.3.101 [Periodic inspec-  IEC/EN 61230, Annex C (informative), C 3.2.2 [It is recommended to
        short-circuiting   equipment is in good order and condition…] tions, general information.] perform a cut test and visual inspection at least every five years in
        devices        (2) [… at certain intervals. The intervals must   case of outdoor use and every ten years in case of indoor use.]
                       be chosen so that the defects to be expected
                       are detected in due time.]
        Voltage detectors,  § 5: according to table 1C    6.2.4 [Inspection at least   IEC/EN 61243-1, Annex G (informative):
        phase comparators  [Tests for compliance with the limit values   before and, if possible,   Tests for capacitive voltage detectors > 1 kV
        and voltage    specified in the electrotechnical rules must   after each use], 5.3.101   [Voltage detectors that have not been subjected to a maintenance
        detecting systems  be carried out at least every six years.]  [Periodic inspections,   test within six years should not be used.]
                                                   general information.]  IEC/EN 61243-5: Tests for voltage detecting systems (VDS)
                                                                    IEC/EN 61481, Annex G (informative):
                                                                    Tests for phase comparators between 1 and 36 kV a.c.
                                                                    [The maximum interval between maintenance tests is six years.]
        Operating and   § 5: according to table 1C    5.3.101 [Periodic inspec-  VDE 0681-1 to 3: Tests for operating sticks
        earthing sticks  [A visual inspection for signs of damage and  tions, general information.] Note: Operating sticks also have to be subjected to electrotech-
                       defects must be carried out prior to each    nical tests. DEHN recommends to use the test intervals of voltage
                       use.]                                        detectors.
                                                                    E DIN VDE V 0681-1 to 3 Annex B (informative)
                                                                    [Maximum interval between maintenance tests for operating sticks
                                                                    is six years.]


                           Part No.  Item
            2025           Periodic Testing of ...
                                  Passive voltage detector for nominal voltages up to 30 kV (all brands) *
                           799 971
                           799 950  Voltage detector for nominal voltages up to 30 kV (all brands) *
         Wiederholungsprüfung
            Nächste        799 951  Voltage detector for nominal voltages exceeding 30 kV [up to 132 kV / 50 Hz] (all brands) *
                           799 952  Voltage detector for overhead contact lines for nominal voltages up to 15 kV (all brands) *
                           799 953  Voltage detector for voltage ranges up to 30 kV (all brands) *
                           799 954  Voltage detector for voltage ranges exceeding 30 kV [up to 132 kV / 50 Hz] (all brands) *
                           799 955  Voltage detector for voltage ranges up to 30 kV – switchable / standby / test kit (all brands) *
                           799 956  Voltage detector for voltage ranges exceeding 30 kV [up to 132 kV / 50 Hz] – switchable / standby (all brands) *
                           799 957  Distance voltage detector (D+S devices only)
                                  Capacitive voltage detecting system (all brands)
                           799 958
                                  Note: Passive voltage indicators are not tested!
                           799 959  Two-pole resistive phase comparator up to 36 kV (D+S devices only) **
                           799 960  Single-pole capacitive phase comparator up to 36 kV (D+S devices only) *
                           799 961  Single-pole capacitive phase comparator (switchable) up to 36 kV (D+S devices only) *
                           799 962  Resistive d.c. voltage detector with one stick (D+S devices only)
                           799 963  Resistive d.c. voltage detector with two sticks (D+S devices only)
                           799 964  Operating stick [fuse tong, insulating stick, switching stick and rescue rod] (all brands)
                           799 965  Operating stick kit (all brands)
                           799 966  Additional test prod for voltage detectors and two-pole phase comparators
                           799 967  Test probe
                           Periodic Testing (visual and technical) of ...
                           799 990  Single-pole earthing and short-circuiting device (Dimension ≤ 8,500 mm)
                           799 991  Three-pole earthing and short-circuiting device (Dimension ≤ 1,000/1,000/1,000 / 2,500 mm)
                           Technical Testing of ...
                           799 992  Earthing stick (all brands)
                           799 993  Test adapter / measuring impedance for capacitive voltage detecting system (all brands)
                           799 994  Earthing and discharge devices

                         * including one test prod / ** including two test prods