Fixed Phase and Earthing Points  EaS Cables  Phase Connecting Elements  Earth Connecting Elements  Earthing Sticks  EaS Devices, Short-Circuiting Bars
           4. Carry out Earthing and Short-Circuiting – EaS Devices

           Cable cross-section:                                  Current carrying capacity of copper short-circuiting cables for
           For short-circuiting cables of our threepole earthing and short-circuiting   use in a.c. and three-phase installations
           devices with cross-sections of 50 mm  and higher, the cross-section of the   kA
                                    2
           earthing cable can be reduced according to the following table.  100
           These earthing and short-circuiting devices with reduced earthing cable
           cross-sections can be used for all non-solidly earthed neutral systems (e.g.   I ‘‘ k  50  42.0 kA
           compensated  systems  with  impedance  neutral  earthing).  For  solidly   30  33.5 kA
                                                                        26.5 kA
           earthed neutral systems, the earthing and short-circuiting cables must   19.5 kA      A = 150 mm
           have the same cross-sections.                                14.0 kA                  A = 120 mm 2 2
           The current carrying capacity of the short-circuiting cable and the short-cir-  10.0 kA  A = 70 mm 2
                                                                                                 A = 95 mm
           cuiting  bar  depends  on  the  material,  the  cross-section  (A)  and  the   10  7.0 kA  A = 50 mm 2
           short-circuit time (Tk).                                                              A = 35 mm 2
           Calculations were based on the most critical case, i.e. an off-generator   5  4.5 kA  A = 25 mm 2
           short circuit (μ = 1) and a maximum d.c. components ( χ  = 1.8) with Ik“   3          A = 16 mm 2
           being the maximum initial short-circuit alternating current, which, accord-                2
           ing to DIN VDE 0102, is equal to the permanent short-circuit current Ik and
           the breaking current Ia:                                  1
                                                                     0.01  0.03 0.05  0.1  0.3  0.5  1  3  5  10 s
                Ik“ = Ik = Ia                                                                            T
                                                                                                          k
           The diagrams or the table help to determine the required cable or busbar  Initial cable temperature  20 °C  Where:
           cross-sections of short-circuiting devices according to the short-circuit     A   Cable cross-section in mm 2
           current and the short-circuit time of an installation.  Final cable temperature  250 °C  Ik“ Maximum initial short-circuit alternating
                                                                 A = 5.07 Ik“ √ Tk   for Tk ≥ 0.5 s  current in kA according to DIN VDE 0102
                                                                                         Tk  Short-circuit time in s


                Cable Cross-Section                              Current carrying capacity of copper short-circuiting cables for
           Short-circuiting  Earthing                            use in d.c. installations
               cable       cable                                    kA
                16 mm 2   16 mm 2                                   100
                                                                        66.9 kA
                25 mm 2   25 mm 2                                 I ‘‘  50  49.6 kA
                35 mm 2   35 mm 2                                  k    35.6 kA
                                                                    30
                50 mm 2   25 mm 2                                       24.8 kA
                70 mm 2   35 mm 2                                       17.5 kA                  A = 95 mm
                95 mm 2   35 mm 2                                       11.2 kA                  A = 70 mm 2
                                                                    10                                2
              120 mm 2    50 mm 2                                                                A = 50 mm 2
              150 mm 2    50 mm 2                                    5                           A = 35 mm 2
                                                                                                 A = 25 mm
                                                                                                      2
                                                                     3                           A = 16 mm
                                                                                                      2
                                                                     1
                                                                     0.01  0.03 0.05 0.08  0.1  0.3  0.5  1  3  5  10 s
                                                                                                         T
                                                                                                          k
                                                                 Initial cable temperature   20 °C  Where:
                                                                 Final cable temperature   250 °C  A   Cable cross-section in mm 2
                                                                                         Ik“ Maximum initial short-circuit alternating
                                                                 A = 5.07 Ik“ √ Tk   for Tk ≥ 0.08 s  current in kA according to DIN VDE 0102
                                                                                         Tk  Short-circuit time in s


                                                                 Current carrying capacity of copper short-circuiting cables for
                                                                 use on overhead contact lines of electric railways
                                                                    kA
                                                                    100
                                                                  I ‘‘  50
                                                                   k
                                                                        34.0 kA
                                                                    30

                                                                    10
                                                                                                                      4. EaS Devices
                                                                                                 A = 50 mm
                                                                                                      2
                                                                     5
                                                                     3

                                                                     1
                                                                     0.01  0.03  0.06  0.1  0.3  0.5  1  3  5  10 s
                                                                                                         T
                                                                                                          k
                                                                                           Where:
                                                                                         A   Cable cross-section in mm 2
                                                                                         Ik“ Maximum initial short-circuit alternating
                                                                  A = 6.0 Ik“ √ Tk   for Tk ≥ 0.06 s  current in kA according to DIN VDE 0102
                                                                                         Tk  Short-circuit time in s
           Valid as of January 1, 2019                       You will find detailed product information on our website   55