        4. Carry out Earthing and Short-Circuiting – EaS Devices

        Calculation example:                                 Table:
        Known:    Mains breaking capacity Sa                 Cable cross-section of the earthing and short-circuiting device depending
                  Short-circuit time Tk                      on the maximum short-circuit Ik and maximum short-circuit time Tk
        Unknown:    Required cable or bar cross-section A.   •  For copper (Cu)
        The calculation is based on an off-generator short-circuit.
                                                              Cross-sec-         Max. short-circuit current Ik
                                                  Sa          tion of the            at a duration of
           Three-phase current     Ik“ = Ik = Ia =  ———        copper
                                            √ 3 • UN            cable   10 s     5 s     2 s     1 s  *)  ≤ 0.5 s  *)
                                                                 16 mm 2  1 000 A    1 400 A    2 200 A    3 200 A    4 500 A
                                               Sa                25 mm 2  1 600 A    2 200 A    3 500 A    4 900 A    7 000 A
          Single-phase alternating current   Ik“ = Ik = Ia =  ——    35 mm 2  2 200 A    3 100 A    4 900 A    6 900 A  10 000 A
                                               UN
                                                                 50 mm 2  3 100 A    4 400 A    7 000 A    9 900 A  14 000 A
        The required cable or bar cross-section can now be calculated based on     70 mm 2  4 400 A    6 200 A    9 800 A  13 800 A  19 500 A
        Ik“ of the above equations or can be taken from the diagrams. The per-    95 mm 2  5 900 A    8 400 A  13 200 A  18 700 A  26 500 A
        missible current carrying capacity of an earthing and short-circuiting de-  120 mm 2  7 500 A  10 600 A  16 700 A  23 700 A  33 500 A
        vice is based on the cross-section printed on the short-circuiting cables or   150 mm 2  9 400 A  13 200 A  20 900 A  29 600 A  42 000 A
        bars.                                                                                        *) catalogue data

        Note:
        –  Earthing and short-circuiting devices can only be loaded once with the
          permissible short-circuit currents depending on the short-circuit time.  •  For aluminium (Al)
        –  Short-circuiting cables of multi-pole earthing and short-circuiting de-  Cross-sec-  Max. short-circuit current Ik
          vices must have the same cross-sections.            tion of the            at a duration of
        –  Cable lengths of earthing and short-circuiting devices should be at   aluminium                  *)
          least 120% of the distance between two fixed connection points. They   cable  10 s  5 s  2 s  1 s  *)  ≤ 0.5 s
          should be as short as possible as the cables move violently during a     35 mm 2  1 400 A    2 000 A    3 200 A    4 600 A    6 500 A
          short-circuit.                                         50 mm 2  2 100 A    2 900 A    4 600 A    6 600 A    9 300 A
        –  When connecting earthing and short-circuiting devices in parallel with     70 mm 2  2 900 A    4 100 A    6 500 A    9 200 A  13 000 A
          cables for achieving certain total cable cross-sections, the following                     *) catalogue data
          conditions must be fulfilled:
          1.  Identical cable lengths and cross-sections,
          2.  Identical connecting clamps and fixed connection points
          3.  Installing the devices directly next to each other, with parallel
            arrangement of cables,
          4.  The current carrying capacity per cable must be reduced to 75% of
            the current carrying capacity of the cable cross-section.

        Remark:
        If it is ensured that earthing and short-circuiting devices connected in
        parallel are loaded with short-circuit currents only once (no interrup tion
        of the short circuit), the devices may be exposed to the full load. Generally,
        this applies to installations with nominal voltages above 110 kV.