Page 72 - dehn-catalogue-safety-equipment_0
P. 72
Fixed Phase and Earthing Points EaS Cables Phase Connecting Elements Earth Connecting Elements Earthing Sticks EaS Devices, Short-Circuiting Bars
4. Carry out Earthing and Short-Circuiting – EaS Devices
Adjustable Ball Head Cap (4x 90°), Hexagon Shaft
772 330 KKH 20 D SK
772 340 KKH 25 D SK
Type KKH 20 D SK KKH 25 D SK
772 330 4013364069220 05 00 04 08 560 g
121,00 €
772 340 4013364057456 05 00 04 08 878 g
153,00 €
Part No. 772 330 772 340
For fixed ball point Ø 20 mm 25 mm
Anti-rotation element PK1 PK1
For cable cross-section Cu 16 ... 120 mm 2 16 ... 150 mm 2
Max. short-circuit current Ik 0.5 s 33.5 kA 42.0 kA
Max. short-circuit current Ik 1 s 23.7 kA 29.6 kA
Adjustable Ball Head Cap (4x 90°), T Pin Shaft
772 331 KKH 20 D SQ
772 341 KKH 25 D SQ
Type KKH 20 D SQ KKH 25 D SQ
772 331 4013364066304 05 00 04 08 566 g
121,00 €
772 341 4013364057425 05 00 04 08 902 g
153,00 €
Part No. 772 331 772 341
For fixed ball point Ø 20 mm 25 mm
Anti-rotation element PK1 PK1
For cable cross-section Cu 16 ... 120 mm 2 16 ... 150 mm 2
Max. short-circuit current Ik 0.5 s 33.5 kA 42.0 kA
Max. short-circuit current Ik 1 s 23.7 kA 29.6 kA
715 314 RBK 25 SQ SN7151
715 315 RBK 26 SQ SN7255 Round Pin Clamp, T Pin Shaft
715 313 RBK 30 SQ SN7642
715 312 RBK 35 SQ
For round pins in switchgear installations.
715 314 4013364132474 05 00 04 06 1.61
kg 230,00 €
715 315 4013364135338 05 00 04 06 1.60
kg 255,00 €
715 313 4013364154971 05 00 04 06 1.55
Type RBK 25 SQ SN7151 RBK 26 SQ SN7255 RBK 30 SQ SN7642 RBK 35 SQ
kg 264,00 €
715 312 4013364150386 05 00 04 06 1.50
kg 231,00 €
Part No. 715 314 715 315 715 313 715 312
For round pins Ø 25 mm 26 mm 30 mm 35 mm
Anti-rotation element PK1 PK1 PK1 PK1
For cable cross-section Cu 16 ... 150 mm 2 16 ... 150 mm 2 16 ... 150 mm 2 16 ... 150 mm 2
Max. short-circuit current Ik 0.5 s 42.0 kA 42.0 kA 42.0 kA 42.0 kA
Max. short-circuit current Ik 1 s 29.6 kA 29.6 kA 29.6 kA 29.6 kA
Universal Clamp, Hexagon Shaft
773 034 UK 25 SK
773 130 UK 30 SK
Type UK 25 SK UK 30 SK
773 034 4013364114562 05 00 04 08 634 g
96,00 €
773 130 4013364057722 05 00 04 08 801 g
97,00 €
Part No. 773 034 773 130
For fixed ball point Ø 20 / 25 mm 25 / 30 mm
For T pins with a collar width of 15 mm 18 mm
Rd / Fl clamping range 20 mm 30 mm
Anti-rotation element PK1 PK1
For cable cross-section Cu 16 ... 120 mm 2 16 ... 120 mm 2
*)
*)
Max. short-circuit current Ik 0.5 s 33.5 kA 33.5 kA
Max. short-circuit current Ik 1 s 23.7 kA 23.7 kA
*) See table for “Clamping range and maximum cable cross-section of universal clamps used for“
Universal Clamp, T Pin Shaft
773 234 UK 25 SQ
773 330 UK 30 SQ
773 234 4013364114555 05 00 04 08 661 g
96,00 €
773 330 4013364057760 05 00 04 08 830 g
97,00 € Type UK 25 SQ UK 30 SQ
Part No. 773 234 773 330
For fixed ball point Ø 20 / 25 mm 25 / 30 mm
For T pins with a collar width of 15 mm 18 mm
Rd / Fl clamping range 20 mm 30 mm
Anti-rotation element PK1 PK1
For cable cross-section Cu 16 ... 120 mm 2 16 ... 120 mm 2
*)
*)
Max. short-circuit current Ik 0.5 s 33.5 kA 33.5 kA
Max. short-circuit current Ik 1 s 23.7 kA 23.7 kA
*) See table for “Clamping range and maximum cable cross-section of universal clamps used for“
4. EaS Devices 771 316 PAS EK SQ 16 Phase Connecting Element, T Pin Shaft *) Clamping range and maximum cable cross-section of
universal clamps used for:
Rd / Fl
Max. cable
With M16 threaded pin for installation in switchgear installations.
Fixed ball point
T Pin
4013364150393 05 00 04 08
418 g
771 316
99,00 €
range
Cu
Type PAS EK SQ 16 Ø Collar width Clamping cross-section
Part No. 771 316 20 / 25 / 30 mm 15 / 18 mm 20 / 30 mm 16 mm 2 2
Dimensions M16 20 / 25 / 30 mm 15 / 18 mm 20 / 30 mm 25 mm 2
Anti-rotation element PK1 20 / 25 / 30 mm 15 / 18 mm 20 / 30 mm 35 mm 2
20 / 30 mm
15 / 18 mm
20 / 25 / 30 mm
50 mm
For cable cross-section Cu 16 ... 150 mm 2 20 / 25 / 30 mm 15 / 18 mm 20 / 30 mm 70 mm 2
Max. short-circuit current Ik 0.5 s 42.0 kA 20 / 25 / 30 mm 15 / 18 mm — 95 mm 2
Max. short-circuit current Ik 1 s 29.6 kA — / 25 / 30 mm — — 120 mm 2
— — — 150 mm 2
The clamps must have the same maximum short-circuit current as the earthing and short-circuiting cables!
70 You will find detailed product information on our website Valid as of January 1, 2019
EaS Devices 4.