Page 158 - B_ELSB_Cat_2022_01_MCBs
P. 158
1/158 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
S300P - S200L @ 415V AC
Supply s. S300P
Char. C
Load s. Icu [kA] 25
In [A] 2 3 4 6 10 16 20 25 32 40 50 63
2 0.3 0.4 0.5 0.6 0.7 0.7 0.8 1.0
3 0.2 0.4 0.5 0.6 0.7 0.7 0.8 1.0
4 0.1 0.3 0.5 0.6 0.7 0.7 0.7 0.9
6 0.03 0.3 0.4 0.5 0.6 0.6 0.6 0.8
8 0.2 0.3 0.4 0.5 0.5 0.5 0.7
10 0.04 0.3 0.4 0.5 0.5 0.5 0.6
13 0.05 0.4 0.5 0.3 0.4 0.5
S200L B 10
16 0.06 0.4 0.4 0.4 0.5
20 0.3 0.4 0.5
25 0.3 0.4 0.5
32 0.4 0.5
40 0.5
50
63
S300P - S200L @ 415V AC
Supply s. S300P
Char. C
Load s. Icu [kA] 25
In [A] 2 3 4 6 10 16 20 25 32 40 50 63
0,5 0.01 0.02 0.02 0.03 0.05 T T T T T T T
1 0.01 0.02 0.02 0.03 0.05 0.7 1.0 1.0 1.3 1.3 1.5 1.7
1,6 0.02 0.03 0.05 0.5 0.8 0.8 1.1 1.1 1.3 1.5
2 0.02 0.03 0.05 0.2 0.3 0.5 0.5 0.5 0.5 0.7
3 0.03 0.05 0.2 0.2 0.4 0.4 0.4 0.5 0.7
4 0.02 0.05 0.2 0.2 0.3 0.3 0.4 0.4 0.5
6 0.05 0.08 0.2 0.3 0.3 0.3 0.5 0.7
8 0.1 0.2 0.2 0.3 0.4 0.7
S200L C 10 10 0.1 0.15 0.2 0.3 0.4 0.5
13 0.15 0.2 0.3 0.4 0.5
16 0.07 0.16 0.3 0.4 0.5
20 0.1 0.3 0.4 0.5
25 0.3 0.4 0.5
32 0.4 0.5
40 0.5
50
63
S300P - S200L @ 415V AC
Supply s. S300P
Char. C
Load s. Icu [kA] 25
In [A] 2 3 4 6 10 16 20 25 32 40 50 63
0,5 0.01 0.02 0.02 0.03 0.05 T T T T T T T
1 0.01 0.02 0.02 0.03 0.05 0.3 0.5 0.7 0.9 0.9 1.3 1.5
1,6 0.02 0.03 0.05 0.2 0.4 0.4 0.5 0.5 1.1 1.5
2 0.02 0.03 0.05 0.08 0.1 0.3 0.5 0.5 1.1 1.5
3 0.03 0.05 0.08 0.1 0.2 0.3 0.5 0.5 1.1
4 0.02 0.05 0.08 0.1 0.15 0.3 0.5 0.5 1.1
6 0.05 0.08 0.1 0.15 0.16 0.3 0.4 0.5
8 0.08 0.1 0.15 0.16 0.3 0.4 0.5
S200L D, K 10 10 0.05 0.1 0.15 0.16 0.2 0.4 0.5
13 0.07 0.16 0.2 0.25 0.5
16 0.1 0.2 0.25 0.4
20 0.1 0.25 0.3
25 0.15 0.3
32 0.2
40
50
63