Page 160 - B_ELSB_Cat_2022_01_MCBs
P. 160
1/160 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
S300P - S200M @ 415V AC
Supply s. S300P
Char. D, K
Load s. Icu [kA] 25
In [A] 2 3 4 6 10 16 20 25 32 40 50 63
2 0.5 0.6 0.7 0.8 0.8 0.9 1.0
3 0.5 0.6 0.7 0.8 0.8 0.9 1.0
4 0.4 0.6 0.7 0.8 0.8 0.8 0.9
6 0.4 0.5 0.6 0.7 0.7 0.7 0.8
8 0.3 0.4 0.5 0.7 0.7 0.6 0.7
10 0.4 0.5 0.6 0.6 0.6 0.6
13 0.4 0.6 0.6 0.5 0.5
S200M B 15
16 0.5 0.5 0.5 0.5
20 0.5 0.5 0.5
25 0.5 0.5 0.5
32 0.5 0.5
40 0.5
50
63
S300P - S200M @ 415V AC
Supply s. S300P
Char. D, K
Load s. Icu [kA] 25
In [A] 2 3 4 6 10 16 20 25 32 40 50 63
0,5 0.02 0.03 0.04 0.06 0.1 T T T T T T T
1 0.02 0.03 0.04 0.06 0.1 0.7 1.0 1.0 1.5 1.5 3.5 5.5
1,6 0.04 0.06 0.1 0.5 0.8 0.8 1.1 1.5 3.5 5.5
2 0.04 0.06 0.1 0.2 0.3 0.5 1.1 1.5 2.6 3.5
3 0.06 0.1 0.2 0.2 0.4 1.1 1.1 1.5 2.6
4 0.03 0.1 0.2 0.2 0.3 1.1 1.1 1.1 1.5
6 0.1 0.2 0.2 0.3 0.5 0.7 1.1 1.5
8 0.2 0.2 0.25 0.5 0.7 1.1 1.5
S200M C 15 10 0.2 0.2 0.25 0.5 0.7 0.9 1.5
13 0.25 0.4 0.5 0.7 1.1
16 0.4 0.5 0.7 1.1
20 0.3 0.5 0.6 1.1
25 0.5 0.6 1.1
32 0.6 0.9
40 0.9
50
63
S300P - S200M @ 415V AC
Supply s. S300P
Char. D, K
Load s. Icu [kA] 25
In [A] 2 3 4 6 10 16 20 25 32 40 50 63
0,5 0.02 0.03 0.04 0.06 0.1 T T T T T T T
1 0.02 0.03 0.04 0.06 0.1 0.5 0.7 0.9 1.5 1.5 3.5 5.5
1,6 0.06 0.1 0.3 0.5 0.7 1.1 1.5 3.5 5.5
2 0.06 0.1 0.2 0.2 0.5 1.1 1.5 2.6 3.5
3 0.06 0.1 0.2 0.2 0.3 1.1 1.1 1.5 1.5
4 0.1 0.2 0.2 0.3 1.1 1.1 1.1 1.5
6 0.2 0.2 0.2 0.5 0.7 1.1 1.5
8 0.2 0.4 0.7 1.1 1.5
S200M D, K 15 10 0.4 0.7 0.9 1.1
13 0.4 0.7 0.7 1.1
16 0.5 0.7 1.1
20 0.6 0.9
25 0.6 0.9
32 0.7
40 0.7
50
63