Page 226 - B_ELSB_Cat_2022_01_MCBs
P. 226

1/226            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          S800-SCL-SR range features




          n Applies for all voltages according to the table below


                                                                S800S-SCL-SR    S803W-SCL-SR    S803HV-SCL-SR
          Rated ultimate short-circuit breaking capacity
          I  = I  according to IEC 60947-2
          cu  cs
          (AC) 50/60 Hz 240/415 V                         kA   100             100
          (AC) 50/60 Hz 254/440 V                         kA   100             100
          (AC) 50/60 Hz 277/480 V                         kA   65              65
          (AC) 50/60 Hz 289/500 V                         kA   65              65
          (AC) 50/60 Hz 346/600 V                         kA   65              65
          (AC) 50/60 Hz 400/690 V                         kA   50              50
          (AC) 50/60 Hz 580/1000 V                        kA                                     I  = 15 kA
                                                                                                cu
                                                                                               I  = 10 kA
                                                                                                cs
          Short-circuit rating according to UL 508, CSA 22.2
          (AC) 50/60 Hz 480 V                             kA                   65
          (AC) 50/60 Hz 600 V                             kA                   65
   221   222   223   224   225   226   227   228