Page 31 - B_ELSB_Cat_2022_01_MCBs
P. 31

1
                                                                                                            1/31



          —
          MCBs technical details
                                                           2
          Limitation of specific let-through energy I t



          S800 S characteristics B, C, D and K
          400 V let-through energy



                                                          200 A
                                                                                  125 A
                            10 5                                                   80 A
                                                    160 A
                                                                                   50 A
                                    Sine-shaped half-wave  100 A 125 A             20 A
                                                                                   32 A
                                                                                   13 A
                          Let-through energy I 2 t [A 2 s]  10 4  63 A  80 A  2


                                        1









                                                                              400 VAC/50 Hz
                                                                                  60˚

                                      2                    10                  50
                                                              Prospective short-circuit current I  [kA]
                                                                                    cc


                                                          200 A
                                                                                  100 A
                            10 5                                                   63 A
                                                    160 A
                                                                                   40 A
                                    Sine-shaped half-wave  100 A 125 A             16 A
                                                                                   25 A
                          Let-through energy I 2 t [A 2 s]  10 4  63 A  80 A
                                                                                   10 A














                                                                              400 VAC/50 Hz
                                                                                  60˚

                                      2                    10                  50
                                                              Prospective short-circuit current I  [kA]
                                                                                    cc
           Min. pre-arching I 2 t, e.g. NH80 A gL/gG
           Max. let-through I 2 t, e.g. S803S-C20
          Selectivity with respect to the upstream fuse to the point of intersection of both curves 1 and 2, e.g.
          S801S-C20 to NH80A gL/gG: Selectivity up to min. 5 kA.
   26   27   28   29   30   31   32   33   34   35   36