Page 34 - B_ELSB_Cat_2022_01_MCBs
P. 34
1/34 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
2
Limitation of specific let-through energy I t
S800 N characteristics B, C and D
230 V let-through energy
200 A 125 A
80 A
10 5
160 A 50 A
32 A
Sine-shaped half-wave
125 A
20 A
13 A
Let-through energy I 2 t [A 2 s] 10 4 63 A 80 A 2
100 A
100 A
1
230 VAC/50 Hz
60˚
2 10 36
Prospective short-circuit current I [kA]
cc
200 A 100 A
10 5 63 A
160 A 40 A
Sine-shaped half-wave
25 A
125 A
16 A
Let-through energy I 2 t [A 2 s] 10 4 63 A 80 A 100 A 10 A
230 VAC/50 Hz
60˚
2 10 36
Prospective short-circuit current I [kA]
cc
Min. pre-arching I 2 t, e.g. NH80 A gL/gG
Max. let-through I 2 t, e.g. S801N-C20
Selectivity with respect to the upstream fuse to the point of intersection of both curves 1 and 2, e.g.
S801N-C20 to NH80A gL/gG: Selectivity up to min. 3.8 kA.