Page 37 - B_ELSB_Cat_2022_01_MCBs
P. 37

1
                                                                                                            1/37



          —
          MCBs technical details
          Limitation of specific let-through energy I t
                                                           2



          S800 C characteristics B, C, D and K
          400 V let-through energy


                                                            200 A
                                                                         125 A
                                10 5                                      80 A
                                                      160 A
                                                                          50 A
                                                 125 A                    32 A
                                                                          20 A
                                                                          13 A
                                                A
                                                 100 A
                                                 100
                              Let-through energy I 2 t [A 2 s]  10 4  63 A  80 A  2
                                          1








                                                                              400 VAC/50 Hz
                                                                              at 60°

                                         2                  10         25
                                                              Prospective short-circuit current I  [kA]
                                                                                    cc








                                                              200 A
                                                                          100 A
                                   10 5                                    63 A
                                                        160 A
                                                                           40 A
                                                   125 A
                                                                           25 A
                                 Let-through energy I 2 t [A 2 s]  10 4  63 A  80 A  10 A
                                                100 A
                                                                           16 A











                                                                               400 VAC/50 Hz
                                                                               at 60°

                                            2                 10        25
                                                              Prospective short-circuit current I  [kA]
                                                                                    cc

           Min. pre-arching I 2 t, e.g. NH80 A gL/gG
           Max. let-through I 2 t, e.g. S803C-C20
          Selectivity with respect to the upstream fuse to the point of intersection of both curves 1 and 2, e.g.
          S801C-C20 to NH80A gL/gG: Selectivity up to min. 3.8 kA
   32   33   34   35   36   37   38   39   40   41   42