Page 103 - Product Catalog V17 - Flip Book PDF
P. 103

Air Circuit Breakers (ACB)



        SWITCH DISCONNECTORS


        Technical Data

         Common data
         Rated service voltage Ue      [V]      690                                                                 1
         Rated insulation voltage Ui   [V]      1000
         Rated impulse withstand voltage Uimp  [kV]  12
         Frequency                     [Hz]     50 - 60
         Number of poles                        3- 4 - 4/f
         Version                                Fixed - Withdrawable
         Suitable for isolation according to    IEC 60947-2


         Frame                        E1.3        E2.3                     E4.3                      E6.3
         Performance levels           B/MS  N/MS  B/MS  C/MS (1)  N/MS  H/MS  C/MS (1)  N/MS  H/MS  V/MS  H/MS  X/MS
         Rated                  [A]   630   250   1600  1600   800    800  3200    3200  3200  2000  4000  4000
         uninterrupted
         current Iu @ 40°C      [A]   800   630   2000  2000   1000   1000  4000   4000  4000  2500  5000  5000
                                [A]   1000  800        2500    1250   1250                     3200  6300  6300
                                [A]   1250  1000               1600   1600                     4000
                                [A]   1600  1250               2000   2000
                                [A]         1600               2500   2500
         Neutral pole           [%Iu]  100  100   100  100     100    100  100     100   100   100   50-100  50-100
         current-carrying   (1s)  [kA]  42  50    42   50      66     85   50      66    85    100   100   120
         capacity
         for 4-pole CBs  (3s)   [kA]  24    30    42   42      50     66   50      50    75 (2)  75  100   100
         Rated short-time   400-415 V  [kA]  88  145  88  145  145    187  145     145   187   220   220   264
         withstand current   440 V  [kA]  88  145  88  145     145    187  145     145   187   220   220   264
         Icw
                        500-525 V  [kA]  88  105  88   105     145    187  110     145   187   220   220   264
                        690 V   [kA]  88   105    88   105     145    187  110     145   187   220   220   264
         Utilization category (according to IEC 60947-2) AC-23A AC-23A AC-23A AC-23A AC-23A AC-23A AC-23A AC-23A AC-23A AC-23A
         1) open only in specific countries;
         2) E4.3H 3200A: 66 Icw (3s)

        Dimensions and weight                      E1.3            E2.3           E4.3           E6.3
        Dimensions     H - Fixed/Withdrawable      296/363.5       371/425        371/425        371/425
                       D - Fixed/Withdrawable      185.5/288.6     277/390        277/390        277/390
                       W - Fixed 3p/4p/4p FS       214/284         276/366        384/510        762/888/1014
                       W - Withdrawable 3p/4p/4p FS  278/348       317/407        425/551        803/929/1069

        Electrical and mechanical life
        Frame                            E1.3           E2.3                 E4.3                E6.3
        Mechanical   [Iu]    [A]         ≤    1250  1600  <   1600  2000  2500  <   2500  3200  4000  4000  5000  6300
        life                             1000           1600                 2500
        with regular
        maintenance          [No. cycles x   20  20  20  25   25   25   20   20   20   20   15   12    12   12
        prescribed           1000]
        by the      Frequency  [Oper./Hour]  60  60  60  60   60   60   60   60   60   60   60   60    60   60
        manufacturer
        Electrical life   440 V  [No. cycles x   8  8  8  15  12   10   8    10   8    7    5    4     3    2
        with                 1000]
        regular     690 V    [No. cycles x   8  6,5  6,5  15  10   8    7    10   8    7    4    4     2    2
        maintenance          1000]
        prescribed
        by the      Frequency  [Oper./Hour]  30  30  30  30   30   30   30   20   20   20   20   10    10   10
        manufacturer








                                                1300 556 601  |  ipd.com.au  |  V17-R12                      103
   98   99   100   101   102   103   104   105   106   107   108