Page 189 - IPD Product Catalog V17
P. 189

Distribution Boards



        CABLE TEE-OFF BOXES


                                                 STANDARD CONFIGURATIONS
        Features:                                Rated Current (A)                                 Part No.
           - Made from 1.5mm Mild Steel
           - Degree of Protection: IP30          Low Cost Fuse Tee-Off box  (1)                                     1
           - Form 1                              100                                               TOB-F100A
           - Orange (X15)                        160                                               TOB-F160A
           - 6mm split Bakelite gland plates     250                                               TOB-F250A
          top and bottom
           - Short circuit fault rating of TOB with fuse is 25kA   Versatile MCCB Tee-Off box  (2)
           - Conditional short circuit fault rating of TOB with   80                               TOB-M080A
          fuse is 25kA and with MCCB is 10kA     100                                               TOB-M100A
                                                 125                                               TOB-M125A
                                                 160                                               TOB-M160A
                                                 200                                               TOB-M200A
                                                 250                                               TOB-M250A
                                                 (1)  Fuse tap off, copper links and line taps are not included. One set of 3 pole fuse disconnectors
                                                  and three fuses are included. Space available for a second set of fuse disconnectors to be
                                                  installed.

                                                 (2)  Single thermal magnetic MCCB, copper links for active, Neutral, Earth and tap-off
                                                  connection between copper links and MCCB are included. Space available for a second
                                                  MCCB to be installed.





                        TOB-M250A


                                                 LINE TAPS
                                                 Maximum Cable Cross Section (mm )                 Part No.
                                                                          2
                                                 16                                                TOB-SB16M6
                                                 35                                                TOB-SB35M6
                                                 70                                                TOB-SB70M6
                                                 95                                                TOB-SB95M6
                                                 185                                               TOB-SB185M6
                         LINE TAPS









                                                 CUSTOM SOLUTIONS
                                                 Contact IPD for a quote for a custom solution.
                                                 The information required is;
                                                   - Riser current rating and cable size.
                                                   - Preferred riser connection method: Copper Links, Line Taps, Other.
                                                   - Tap off current rating and qty: 1 or 2 per TOB.
                                                   - Preferred tap off protection: Fuse or MCCB.

















                                               1300 556 601  |  ipd.com.au  |  V17-R05                       189