Page 257 - IPD Product Catalog V17
P. 257
Lightning & Surge Protection
PROCESS CONTROL PROTECTION - DATA & COMMUNICATION
DEHN BLITZDUCTORCONNECT SELECTION GUIDE FOR DATA SIGNAL PROTECTION
Type 1 Lightning Current Arrestors
BCO Compact BCO Modular BCO Compact BCO Modular 1
Interface Signal Article No. Article No. Interface Signal Article No. Article No.
0 - 20 mA, 4 - 20 mA 927944 927244 PROFIBUS-PA Ex(i) 927984 927284
Binary signals 927924 927224 RS 422 927971 927271
Ex(i) measuring circuits 927984 927284 RS 485 927971 927271
Fieldbus Foundation 927944 927244 Temperature measurement 927922 927222
Fieldbus Foundation Ex(i) 927984 927284 TTL 927922 927222
Modbus RTU 927971 927271 TTY 4 - 20 mA 927924 927224
PROFIBUS-DP/FMS 927971 927271 Video (2-wire) 927971 927271
PROFIBUS-PA 927944 927244 xDSL 927910 927210
DEHN BLITZDUCTORCONNECT – COMPACT
Features: Total
- Din Mount In (8/20μs) Iimp (10/350μs) per MCOV SPD Article No. Part No.
- Space-saving (kA) Line (kA) AC (V) DC (V) Type
- Push-in connection technology 6 8.5 927970 BCOCL2BEHF5
- Width of 6 mm
- Test standards IEC 61643-21/ 6 8.5 927971 BCOCL2BDHF5
EN 61643-21 10.6 15 927922 BCOCL2BE12
10.6 15 927942 BCOCL2BD12
23.3 33 927924 BCOCL2BE24
10 1.5 1
25.4 36 927944 BCOCL2BD24
25.4 36 927984 BCOCL2BDEX24 (1)
38.1 54 927925 BCOCL2BE48
39.6 56 927945 BCOCL2BD48
127 180 927910 BCOCL2B180
(1) Intrinsically safe
BCOCL2BE12
DEHN BLITZDUCTORCONNECT – MODULAR
Features: Total
- Din Mount In (8/20μs) Iimp (10/350μs) per MCOV SPD Article No. Part No.
- Space-saving (kA) Line (kA) AC (V) DC (V) Type
- Push-in connection technology 6 8.5 927270 BCOML2BEHF5
- Width of 6 mm
- Test standards IEC 61643-21/ 6 8.5 927271 BCOML2BDHF5
EN 61643-21 10.6 15 927222 BCOML2BE12
10.6 15 927242 BCOML2BD12
23.3 33 927224 BCOML2BE24
10 1.5 1
25.4 36 927244 BCOML2BD24
25.4 36 927284 BCOML2BDEX24 (1)
38.1 54 927225 BCOML2BE48
39.6 56 927245 BCOML2BD48
127 180 927210 BCOML2B180
(1) Intrinsically safe
BCOML2BD48
NOVARIS RJ MODULAR PLUG PROTECTION
Features: MCOV Voltage Protection
- For twisted pair Imax (8/20μs) No.of Pairs Level (1 kV/μs) Maximum Load Part No.
telecommunication services (kA) AC (V) DC (V) - Up Current (mA)
- Multistage protection 1 MPP-RJ12-1
- Metal enclosure 10 140 200 <0.15 350
2 MPP-RJ45
MPP-RJ12-1
1300 556 601 | ipd.com.au | V17-R05 257