Lightning & Surge Protection







 Surge I    Lightning I                                                                       Recommended Maximum
 Config  Zone Boundary  SPD Location  Type/class  max  imp  Model style/mounting  Voltage Protection Level Up  Model Style/Mounting  Voltage Protection Level Up
 8/20μs  10/350μs                                                                             Backup Protection
                                                                                                      500 A aG
 Main switchboard  50 kA                                SG3-50-275       ≤ 1.3 kV                     XLP3-6M12
 Distribution board  Type 1                             Spark gap-DIN    1.2/50µs                     3 x NHG2-500  1
 LPZ 0A/1  Service entrance  Class I
 High lightning area (Ng>5)   Lightning  DVCI 1 255-TNC                                       Integrated fuse
 Location category C3  protection  25 kA  Spark gap-DIN mtg  ≤ 1.5 kV                         external backup not
                                                                                              required
 DVACSP1P255FM (x3)                                                                                   125 A gG
 250 kA  25 kA  EBDG100013   ≤ 1.5 kV                                                                 3 x CMS221
 Spark gap-DIN mtg                                                                                    3 x 22G125
                                                                                                      100 A gG
                                                        SD3-200-275
 200 kA  25 kA                                                           ≤ 1.7 kV                     3 x CMS221
                                                        MultiMOV-panel
 Main switchboard  Type 1 + 2                                                                         3 x 22G100
 Service entrance  Class I + II  150 kA  19 kA          SD3-150-275      ≤ 1.6 kV                     80 A gG
                                                                                                      3 x CMS221
 Combined
 Sub switchboard
 MEN Link installed  LPZ 0A/1  High lightning area (Ng>2)  protection  125 kA  12.5 kA  DSH TNC 255 FM   ≤ 1.5 kV  125 A gG
                                                        MultiMOV-panel
                                                                                                      3 x 22G80
 lightning
 Distribution board
 and surge
 Industrial and commercial
                                                                                                      3 x CMS221
 Spark gap-DIN mtg
 current
 Long service lines
                                                                                                      3 x 22G125
 arrester
 Location category C2 or C3
                                                        SD3-100-275
                                                                                                      3 x CMS221
 12.5 kA
 100 kA
                                                        MultiMOV-panel   ≤ 1.5 kV                     63 A gG
                                                                                                      3 x 22G63
                                                                                                      63 A gG
                                                        IDD3-100-D480
 100 kA  12.5 kA                                                         ≤ 1.5 kV                     3 x CMS221
                                                        MOV-DIN
                                                                                                      3 x 22G63
                                                                                                      32 A gG
 DGM TNC 385 CN FM                                      IDD3-50-D480
 Domestic service entrance  50 kA  MOV-DIN mtg  ≤ 1.5 kV  MOV-DIN        ≤ 1.5 kV                     3 x CMS221
 Services shielded  Type 2                                                                            3 x 22G32
 from direct strike                                                                           Integrated fuse
 LPZ 0B/1  Class II  DGM TNC ACI 275 FM
 LPZ 1/2  Major submains  Surge current  40 kA  MOV-DIN mtg  ≤ 1.5 kV                         external backup not
 Short final subcircuits  arrester                                                            required
 Load centres                                                                                         125 A gG
 Location category B or C1  40 kA  DGM TNC 275 FM   ≤ 1.5 kV                                          3 x CMS221
 MOV-DIN mtg
                                                                                                      3 x 22G125
                                                                                                      500 A aG
 Main switchboard  Type 1  50 kA                        SG3-50-275-N     ≤ 1.3 kV                     XLP3-6M12
 Distribution board  Class I                            Spark gap-DIN mtg  1.2/50µs                   3 x NHG2-500
 LPZ 0A/1  Service entrance  Lightning
 High lightning area (Ng>5)   protection  DVCI 1 255-TT                                       Integrated fuse
 Location category C3  25 kA  Spark gap-DIN mtg  ≤ 1.5 kV                                     external backup not
                                                                                              required
 DVACSP1P255FM(x3)                                                                                    125 A gG
 250 kA  25 kA  DGPM1255FM(x1)  ≤ 1.5 kV                                                              3 x CMS221
 EB1413                                                                                               3 x 22G125
                                                                                                      100 A gG
                                                        SDN3-200-275
 200 kA  25 kA                                                           ≤ 1.7 kV                     3 x CMS221
                                                        MultiMOV-DIN                                  3 x 22G100
 Main switchboard  Type 1 + 2
 Service entrance  Class I + II  150 kA  19 kA          SDN3-150-275     ≤ 1.6 kV                     80 A gG
 NO MEN Link installed  LPZ 0A/1  High lightning area (Ng>2)  protection  125 kA  12.5 kA  DSH TT 255 FM  ≤ 1.5 kV  ≤ 1.6 kV  125 A gG
                                                                                                      3 x CMS221
 Sub switchboard
 Combined
                                                        MultiMOV-DIN
                                                                                                      3 x 22G80
 lightning
 Distribution board
 Industrial and commercial
 and surge
                                                                                                      3 x CMS221
 Spark gap-DIN mtg
 current
 Long service lines
                                                                                                      3 x 22G125
 Location category C2 or C3
 arrester
                                                                                                      63 A gG
                                                        SDN3-100-275
                                                                                                      3 x CMS221
 12.5 kA
 100 kA
                                                                         ≤ 1.5 kV
                                                        MultiMOV-DIN
                                                                                                      3 x 22G63
                                                                                                      63 A gG
                                                        SDD3-100-275-A
 100 kA  12.5 kA                                                         ≤ 1.5 kV                     3 x CMS221
                                                        MOV-DIN
                                                                                                      3 x 22G63
 Domestic service entrance  DGM TT 385 CN FM            SDD3-50-275-A                                 32 A gG
 Distribution boards  50 kA  MOV-DIN mtg  ≤ 1.5 kV      MOV-DIN          ≤ 1.5 kV                     3 x CMS221
 Consumer units  Type 2                                                                               3 x 22G32
 Load centres                                                                                 Integrated fuse
 LPZ 0B/1  Class II  DGM TT ACI 275 FM
 LPZ 1/2  Services shielded from  Surge current  40 kA  MOV-DIN mtg  ≤ 1.5 kV                 external backup not
 direct strike                                                                                required
 Major submains  arrester                                                                             125 A gG
 Short final subcircuits  40 kA  DGM TT 275 FM  ≤ 1.5 kV                                              3 x CMS221
 Location category B or C1  MOV-DIN mtg                                                               3 x 22G125
                                                1300 556 601  |  ipd.com.au  |  V17-R12                      253