Switchboard Systems



        EXT56 - OUTDOOR SWITCHBOARD SOLUTIONS


         General Data



          Applications:             Low voltage power switchgear and control gear assemblies, power distribution boards, Motor control centres,
                                    PLC & DCS panel boards.
          Installation:             Outdoor
          Mounting possibilities:   Floor Standing
          Standard Colours:         Grey (RAL 7032) / Orange (RAL 2000) frame and X15 / Grey (RAL 7032) / Sand finish aluminium cladding .
                                                                                                          (1)
          Standard:                 AS/NZS 61439-1:2016
          Coating:                  Epoxy / Polyester powder, Thickness > 50 μm smooth
          Material:                 Frame : 2mm electro-galvanised mild steel (1)
                                    Frame collar : 2mm Marine grade aluminium 5052 H32 (1)
                                    Doors, Covers and Rainhoods : 3mm Marine grade aluminium 5052 H32 (1)
                                    Plinth : 3mm mild steel hot dipped galvanized
          (1)  Powder coated cladding on request.








         Mechanical Data


          Field / Tier Arrangement:  Front connected
          Cable entry:              Bottom
          Compartment types:        Fixed
          Access:                   Front / Rear
          Degree of Protection:     IP56 (Outdoor)
          Form of segregation:      1, 2a, 2b, 3a, 3b, 4a, 4b
          Maximum dimensions of a transport   Width - 2400mm (Extendable)
          section (Basic module 200x200x200): Height - 2000mm (Maximum)
                                    Depth - 800mm







         Electrical Data



          Rated operational voltage (Ue):  Up to 1000V
          Rated frequency (f):      50Hz
          Rated impulse voltage (Uimp):  Up to 12 kV
          Rated current (In) for TM   Up to 3200A (Refer to the Elsteel CM for more information)
          panels(Uimp):
          Rated short time current (lcw):  Up to 100kA/1s & 80kA/3s (Refer to the Elsteel CM for more information)
          Min. clearance and creep age:  (Refer to the Elsteel CM for more information)
          Earthling systems:        TN-C, TN-S, TN-C-S, TT, IT
          Internal Arc Fault Containment:  Acc. to AS/NZS 61439-1:2016 Appendix ZD










         340                                     1300 556 601  |  ipd.com.au  |  V17-R05