Page 367 - IPD Product Catalog V17
P. 367
Metal Enclosures
FLEXIBARS
FLEXIBAR SUPPORT HOLDER
Description Qty. Part No.
Flexibar Support Holder 3 Pole 160A/250A/400A 1 Set FCSH21164
- The short circuit protective device must interrupt the short-circuit current within 10 milliseconds
and limit the peak cut-off current to be within the values given above.
Fault Current Maximum Spacing
FCSH21164
(Prospective) Centres (1)
50kA 500mm
63kA 280mm
(1) For conditional short circuit applications only.
3
BUSBAR TAP-OFF ACCESSORIES
Description Size Qty. Part No.
Tap Off Set Ø 10mm 1 Set TOS21010
Tap Off Bracket 6 x M5 1 Set TOB21020
1300 556 601 | ipd.com.au | V17-R05 367