Page 756 - IPD Product Catalog V17
P. 756

PV Solutions


        STANDALONE RELAYS



                                             CM-UFD.M33 (VOLTAGE BASED)
        Features:                                                        Voltage AC/DC
           - Monitoring of voltage and frequency in single and   Description  (V)      Width         Part No.
          three-phase mains ,                 Grid Monitoring Relay                                  CM-UFD.M33
          (2-wire, 3-wire or 4-wire AC systems)   Grid Monitoring with Modbus output  24 - 240  6 Modules (108mm)  CM-UFD.M33M
           - Error memory for up to 99 entries (including cause
          of error, measured value, relative timestamp)
           - Pre-settings in accordance with G59/3 and G83/2
           - Integrated management of redundancy function
           - Multiline, backlit LCD display
           - True RMS measuring principle
           - Over- and under voltage, 10-minutes average
          value as well as over- and under frequency
          monitoring
           - Two-level threshold settings for over/undervoltage
          and over/under frequency
           - ROCOF (rate of change of frequency) monitoring
          and vector shift configurable
           - Interrupted neutral detection
           - All threshold values and tripping
          delays adjustable
           - Test function
           - Password setting protection
           - 3 control inputs, e.g. for feedback signal,
          remote trip
           - 3CO (SPDT) contacts
           - Australian utility approvals
           - ANSI Codes, 59, 27, 81H, 81L, 78, 81R

















































          756                                    1300 556 601  |  ipd.com.au  |  V17-R05
   751   752   753   754   755   756   757   758   759   760   761