Page 85 - Product-catalogue-v17
P. 85

Air Circuit Breakers (ACB)



        SACE EMAX 2 AUTOMATIC AIR CIRCUIT BREAKERS


         Technical Data

         Common data
         Rated Service Voltage Ue      [V]  690                                                                     1
         Rated Insulation Voltage Ui   [V]  1000
         Rated Impulse Withstand Voltage Uimp  [kV] 12
         Frequency                     [Hz] 50 - 60
         Number of Poles                   3 - 4
         Version                           Fixed - Withdrawable
         Suitable for Isolation According to:  IEC 60947-2






         SACE Emax 2                                          E1.2    E2.2          E4.2          E6.2
         Performance levels                                   N       N      H      N      H      H
         Rated Uninterrupted Current Iu @ 40°C   [A]          250     800    800    3200   3200   4000
                                                 [A]          630     1000   1000   4000   4000   5000
                                                 [A]          800     1250   1250                 6300
                                                 [A]          1000    1600   1600
                                                 [A]          1250    2000   2000
                                                 [A]          1600    2500   2500
         Neutral Pole Current-carrying Capacity for 4-pole CBs  [%Iu]  100  100  100  100  100    50-100
         Ultimate Short-Circuit  400-415 V       [kA]         66      66     100    66     100    100
         Breaking Capacity Icu  690 V            [kA]         50      66     85     66     85     100
         Rated Service Short-Circuit Breaking Capacity Ics  [%Icu]  100  (1)  100  100  100  100  100
         Short-time Withstand  (1s)              [kA]         50      66     85     66     85     100
         Current Icw         (3s)                [kA]         30      50     66     50     75  (2)  100
         Rated Short-Circuit Making 400-415 V    [kA]         145     145    220    145    220    220
         Capacity (Peak Value) Icm  690 V        [kA]         105     145    187    145    187    220
         Utilization Category (according to IEC 60947-2)      B       B      B      B      B      B
         Breaking            Breaking Time for I<Icw  [ms]    40      40     40     40     40     40
                             Breaking Time for I>Icw  [ms]    25      25     25     25     25     25
         Dimensions          H - Fixed/Withdrawable  [mm]     296/363.5 371/425  371/425  371/425  371/425  371/425
                             D - Fixed/Withdrawable  [mm]     183/271  270/383  270/383  270/383  270/383  270/383
                             W - Fixed 3p/4p/4p FS  [mm]      210/280  276/366      384/510       762/888/1014
                             W - Withdrawable 3p/4p/4p   [mm]  278/348  317/407     425/551       803/929/1069
                             FS
         Weights (CB with Trip Unit   Fixed 3p/4p  kg         14/16   41/53         56/70         109/125/140
         and Current Sensor)  Withdrawable 3p/4p/4p   kg      38/43   84/99         110/136       207/234/260
                             FS including Fixed Part
         (1)  Ics : 50kA for 400V - 440V voltage
         (2)  E4.2H 3200A: 66 Icw (3s)



         SACE Emax 2                                          E1.2    E2.2          E4.2          E6.2
         Mechanical Life with Regular Maintenance as prescribed  [Iu]  1600  1600  2500  < 2500  3200  4000
         by Manufacturer                         [No. cycles x 1000] 20  25  20     20     20     12
                             Frequency           [Oper./Hour]  60     60     60     60     60     60
         Electrical Life with Regular   440V     [No. cycles x 1000] 8  12   8      10     7      4
         Maintenance as prescribed   690V        [No. cycles x 1000] 6,5  10  7     10     7      4
         by Manufacturer
                             Frequency           [Oper./Hour]  30     30     30     20     20     10





                                               1300 556 601  |  ipd.com.au  |  V17-R04                       85
   80   81   82   83   84   85   86   87   88   89   90