Air Circuit Breakers (ACB)



        AIR CIRCUIT BREAKERS


         Technical Characteristics for Protection Trip Units - Measurement Functions


                                                                                                                    1

         Instantaneous measurements     Parameters                           Precision (Class 1) (1)  Ekip Touch (2)  Ekip Hi-Touch
         Currents (RMS)           [A]   L1, L2, L3, Ne                       0.5%                ●         ●
         Earth Fault Current (RMS)  [A]  Ig                                  2%                  ●         ●
         Phase-Phase Voltage (RMS)  [V]  U12, U23, U31                       0.5%                ●         ●
         Phase-Neutral Voltage (RMS)  [V]  U1, U2, U3                        0.5%                ●         ●
         Phase Sequence                                                                          ●         ●
         Frequency                [Hz]  f                                    0.1%                ●         ●
         Active Power             [kW]  P1, P2, P3, Ptot                     1%                  ●         ●
         Reactive Power           [kVAR]  Q1, Q2, Q3, Qtot                   2%                  ●         ●
         Apparent Power           [KVA]  S1, S2, S3, Stot                    1%                  ●         ●
         Power Factor                   total                                2%                  ●         ●
         Peak Factor                    L1, L2, L3, Ne                                           ●         ●

         Counters Recorded from Installation or from   Parameters            Precision (Class 1) (1)
         the Last Reset
         Active Energy            [kWh]  Ep total, Ep positive, Ep negative  1%                  ●         ●
         Reactive Energy          [kVARh]  Eq total, Ep positive, Ep negative  2%                ●         ●
         Apparent Energy          [KVAh]  Es total                           1%                  ●         ●

         Network Analyser               Parameters                           Intervals
                                        - Umin = 0.75...0.95 x Un
                                  [V]   - Umax = 1.05...1.25 x Un
         Hourly Average Voltage Value                                        t = 5...120min      ●         ●
                                  [No.]  - Events counter (No. of events day by day in the last
                                           year plus the total events in the breaker’s lifetime)
                                        - Umin = 0.75...0.95 x Un
         Short Voltage Interruptions  [No.]  - Events counter (No. of events day by day in the last        t < 40ms  ●  ●
                                           year plus the total events in the breaker’s lifetime)
                                        - Umax = 1.05...1.25 x Un
         Short Voltage Spikes     [No.]  - Events counter (No. of events day by day in the last   t < 40ms  ●  ●
                                           year plus the total events in the breaker’s lifetime)
                                        - Umin1 = 0.75...0.95 x Un
                                        - Umin2 = 0.75...0.95 x Un
                                        - Umin3 = 0.75...0.95 x Un
         Slow-Voltage Sags and Swells  [No.]  - Umax1 = 1.05...1.25 x Un     t = 0.02s...60s     ●         ●
                                        - Umax2 = 1.05...1.25 x Un
                                        - Events counter (No. of events day by day in the last
                                           year plus the total events in the breaker’s lifetime)
                                        - U neg. seq.=0.02...0.10 x Un
                                  [V]
         Voltage Unbalance              - Events counter (No. of events day by day in the last   t = 5...120min  ●  ●
                                  [No.]
                                           year plus the total events in the breaker’s lifetime)
                                        Current and Voltage
                                        - Up to 50 o
                                        - Alarm THD: 5...20%
         Harmonic Analysis                                                                       ●         ●
                                        - Single harmonic alarm:
                                           3...10% plus a count of minutes the harmonic
                                           has been exceeded
        (1)  Class 1 is factory fitted and not available on stock standard breakers. Contact IPD
        (2)  Precision (Class 1) available with dedicated extracode
        With Class 1, please refer to the precision values below:
          Current (RMS)         1%             Frequency             0.2%           Power Factor          2%
          Earth Fault Current (RMS)  2%        Active Power          2%             Active Energy         2%
          Phase-Phase Voltage (RMS)  0.5%      Reactive Power        2%             Reactive Energy       2%
          Phase-Neutral Voltage (RMS)  0.5%    Apparent Power        2%             Apparent Energy       2%