To be able to safely leave a structure in case of fire, escape   Structure with non-metal roof and external
       routes must be kept free of smoke which causes orientation   lightning protection system
       and breathing problems.                      Embedded or protruding roof-mounted structures on struc-
       Smoke and heat extraction systems are both equipped with   tures with external lightning protection system must be locat-
       manual call points and automatic detectors which detect the   ed in the protected volume of air-termination systems as per
       smoke or heat produced and extract it from the escape route   IEC 62305-3 (EN 62305-3) under consideration of the separa-
       via electromechanically or pneumatically driven windows or   tion distance s if the following limit values are exceeded:
       domelights. In addition to this main function, the windows or
       domelights are also used for ventilation. For this purpose, ad-  Embedded or protruding metal roof-mounted structures:
       ditional switching devices are available which are capable of
       issuing switching commands of lower importance. Since the   ¨  Height above the roof level: 0.3 m
       availability of smoke and heat extraction systems must be en-  ¨  Total area of the roof-mounted structure: 1.0 m²
       sured even in the event of power failure, the fire control panels   ¨  Length of the roof-mounted structure: 2.0 m
       are equipped with accumulators which supply the smoke and
       heat extraction systems. Therefore, the actuators of the win-  Embedded or protruding non-metal roof-mounted structures:
       dows and domelights are dimensioned for d.c. operation.
                                                    ¨  Height above the air-termination system: 0.5 m
       The surge protective devices in the examples described below
       are dimensioned based on a voltage of 24 V d.c. which is com-  Due to the above requirements, domelights of a certain size
       monly used in this industry. Moreover, electromechanically   must be protected against lightning strikes. If air-termination
       driven domelights with a maximum nominal current of less   rods are installed, the domelights are located in LPZ 0 B  which
       than 1.8 A or 4 A d.c. are used.             means that no lightning current is injected into the equipment


                 motor
                 24 V d.c. < 4 A     protective angle α
                                                wind / rain sensor
             smoke detector                                    No.  Surge protective device Part No.
                                                                   DG M TN 275 (TN-S system)  952 200
                                                                   DG M TT 2 P 275 (TT system)  952 110
                                                                   BXT ML4 BE 24        920 324
        fire control     3*                                         + BXT BAS            920 300
        panel           2*
                        4*
                                                                   2 x BXT ML4 BE 24    920 324
                                                                   + 2 x BXT BAS        920 300
                                230 V / 50 Hz
                                                                   BXT ML4 BE 36 (1.8 A)   920 336
                                                                   + BXT BAS or         920 300
                                                                   2 x BVT ALD 36 (4 A)  918 408
                       6*  4* (6*)
                                                                   BXT ML2 BE S 24      920 224
                       SDS  VS                                     + BXT BAS            920 300
                                                                 =

                       6*
                           4* (6*)                             Alternative
                                                                   TL2 10DA CC          907 991
                       SDS  VS                                     DRL 10 B 180 FSD     907 401
                                                                   EF 10 DRL            907 498
                                                                   8 x DRL RE 24        907 422
                                                               * Minimum number of required cores
                                                                 (observe manufacturers’ instructions)
       Figure 9.27.1  Domelight located in the protected volume of an air-termination rod on a non-metal roof of a structure with external lightning
                protection system



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  411