Page 413 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 413

motor
                           24 V d.c. < 4 A  protective angle α  wind / rain sensor


                     smoke detector
                                                                 No.  Surge protective device Part No.
                                                                      DG M TN 275 (TN-S system)  952 200
                 fire control                                          DG M TT 2 P 275 (TT system)  952 110
                 panel
                                  3*                                  BXT ML4 BE 24        920 324
                                  2*
                                  4*                                  + BXT BAS            920 300
                                                                      2 x BXT ML4 BE 24    920 324
                                         230 V / 50 Hz                + 2 x BXT BAS        920 300
                                                                      BXT ML4 BE 36 (1.8 A)   920 336
                                                                      + BXT BAS or         920 300
                                6*  4* (6*)                           2 x BVT ALD 36 (4 A)  918 408
                                                                      BXT ML2 BE S 24      920 224
                                SDS  VS                               + BXT BAS            920 300

                                                                    =

                                6*
                                    4* (6*)
                                                                 Alternative
                                SDS  VS                               TL2 10DA CC          907 991
                                                                      DRL 10 B 180 FSD     907 401
                                                                      EF 10 DRL            907 498
                                                                      8 x DRL RE 24        907 422
                                                                 * Minimum number of required cores
                                                                   (observe manufacturers’ instructions)
          Figure 9.27.2  Domelight located in the protected volume of an air-termination rod on a metal roof of a structure with metal down conductor
                   (steel frame, interconnected reinforced concrete or earthed metal facade)

          installed in this zone (Figure 9.27.1). A surge arrester pre-  be interconnected by means of lightning current carrying
          vents inductive coupling in this zone.         conductors if there is no other lightning current carrying
                                                         connection (e.g. by means of tested terminals, brazing,
          Structure with metal roof and external lightning   welding, squeezing, seaming, screwing or riveting).
          protection system                            3.  The metal roof has the required thickness t (IEC 62305-3
          In contrast to structures with non-metal roofs and external   (EN 62305-3), Table 3)
          lightning protection system, different normative require-
          ments are placed on the lightning current carrying capability   There are two types of down conductors for the metal roofs
          of metal roofs which are used as air-termination system:  described before:
          1.  The  metal  roof  can  be  used  as  natural air-termination   A.  The walls consist of an interconnected lightning current
            system if the manufacturer confirms that it suited for this   carrying steel reinforcement or a steel frame construc-
            purpose (DIN EN 62305-3, Supplement 4).      tion. In both cases, the separation distance does not have
          2.  The metal roof does not have the required thickness t’   to be considered since either the current is very low due
            (IEC 62305-3 (EN 62305-3 ), Table 3) and must be pro-  to the high number of current paths (reinforcements) or
            tected against direct lightning strikes by means of air-  the low inductance (steel beams) does not cause punc-
            termination systems since perforation can cause fire due   ture to other metal systems. Metal façades which are
            to the highly flammable materials (or wooden boards)   connected to the earth-termination system at intervals of
            underneath the tin roof and the ingress of water can no   15 m at the lowest point (ground) also meet the require-
            longer be prevented. The air-termination systems  must   ments described above.



          412  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com