Page 425 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 425

control unit


                                                         con-
                                                         troller
                                    power supply

                  temperature
                  sensor
                                                                       heating cable



                                                     moisture sensor


                                                              Type                     Part No.
                                                              DG M TT 2P 275 (TT/TN-S system)  952 110
                                                              DG M TT 275   (TT/TN-S system)  952 310
                                                              BXT ML2 BE S 5            920 220
                                                              + BXT BAS                 920 300
                                                              DSH TT 2P 255 (TT/TN-S system)  941 110
                                                              DSH TN 255 (TN-S system)  941 200


          Figure 9.29.2  Installation of lightning current and surge arresters if the control unit is located far from the entry point into a structure with
                   external lightning protection system

          splits both between the down conductors directly connected   tion. If the air-termination systems ensure that the cables be-
          to the metallic gutter and the down conductors connected to   yond the roof are not hit by a lightning strike, surge protective
          the air-termination mesh. Even if the external lightning protec-  devices according to Figure 9.29.1 can be used.
          tion system only has four down conductors, lightning currents
          of less than 10 to 12 kA per core are to be expected in case of   If loss of the control unit is acceptable (the control unit and / or
          LPL III. A type 2 surge arrester must be provided in the feeder   the incoming cables must not present a risk of fire), the struc-
          cable upstream of the control unit (Figure 9.29.2).  ture can be protected by installing combined arresters directly
                                                       at the point where the cables enter the structure (Figure
          Buildings with an interconnected reinforced concrete or steel   9.29.3).
          frame construction (IEC 62305-4 (EN 62305-4)) are an excep-

















          424  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com
   420   421   422   423   424   425   426   427   428   429   430