Page 18 - ACB-E1.2-E2.2-E4.2-E6.2
P. 18

ABB | SACE Emax 2

       3 - Graphic pages



                        Histograms The page displays the histograms of the current and voltage measurements acquired in real time and
                                    certain status information:
















                                    Figure 9

                                     Pos.  Description
                                           Up to four information icons are available:
                                                       The letter corresponding to the active configuration is displayed if Adaptive
                                               or      Protections package is present and with Dual Set enabled;
                                                       External power supply present (Vaux or through a service connector); the
                                               or      plug icon indicates Vaux
                                     A                 Remote parameter writing configuration activre, modules Ekip Com
                                                       connected, Vaux present
                                                       Bluetooth antenna state; four options available, see next chapter for details

                                                       Datalogger active
                                           Histograms of the voltage and current measurements acquired in real time.
                                           The bar of each signal is represented in scale 0 to 125 % with reference to the rated current
                                           and voltage values of the, and can be of three colors:
                                            • light blue: no protection in alarm status
                                     B
                                            • yellow: one of the tripped protections is in prealarm status with respect to set thresholds
                                            • red: one of the tripped protections is in alarm status with respect to set thresholds
                                              NOTE: Histogram Ne is available with 4P or 3P + N configurations

                                     C     Maximum phase current measured in real time
                                     D     Maximum line-to-line voltage measured in real time




                     Summary page Press on the sides of the display (1) from the Home page to access further summary pages for certain
                                    measurements:
                                     •  Main measurements page: maximum phase current, maximum line-to-line voltage, power factor,
                                       total active/reactive/apparent powers
                                     •  Ekip Synchrocheck main measurements page (when module is present): Int and Ext frequencies
                                       and voltages, phase difference, synchronism status (page 21)















                                    Figure 10
                                           NOTE: both pages can be set as the main page by pressing HOME, holding it for five
                                           seconds and confirming the message on the display

       16 | © 2022 ABB |  1SDH001316R1002 - ECN000232533                    Ekip Touch - Interface and menus | 3 - Graphic pages
   13   14   15   16   17   18   19   20   21   22   23