Page 18 - ACB-E1.2-E2.2-E4.2-E6.2
P. 18
ABB | SACE Emax 2
3 - Graphic pages
Histograms The page displays the histograms of the current and voltage measurements acquired in real time and
certain status information:
Figure 9
Pos. Description
Up to four information icons are available:
The letter corresponding to the active configuration is displayed if Adaptive
or Protections package is present and with Dual Set enabled;
External power supply present (Vaux or through a service connector); the
or plug icon indicates Vaux
A Remote parameter writing configuration activre, modules Ekip Com
connected, Vaux present
Bluetooth antenna state; four options available, see next chapter for details
Datalogger active
Histograms of the voltage and current measurements acquired in real time.
The bar of each signal is represented in scale 0 to 125 % with reference to the rated current
and voltage values of the, and can be of three colors:
• light blue: no protection in alarm status
B
• yellow: one of the tripped protections is in prealarm status with respect to set thresholds
• red: one of the tripped protections is in alarm status with respect to set thresholds
NOTE: Histogram Ne is available with 4P or 3P + N configurations
C Maximum phase current measured in real time
D Maximum line-to-line voltage measured in real time
Summary page Press on the sides of the display (1) from the Home page to access further summary pages for certain
measurements:
• Main measurements page: maximum phase current, maximum line-to-line voltage, power factor,
total active/reactive/apparent powers
• Ekip Synchrocheck main measurements page (when module is present): Int and Ext frequencies
and voltages, phase difference, synchronism status (page 21)
Figure 10
NOTE: both pages can be set as the main page by pressing HOME, holding it for five
seconds and confirming the message on the display