Continued from the previous page                                ABB | SACE Emax 2
                                    Ekip Touch configuration involves certain exceptions:
                                     •  the Ne current measurements are available with 4P and 3P + N configurations
                                     •  the phase voltage measurements are available with the 4P and 3P + active external neutral voltage
                                       configuration
                                     •  with the 3P configuration, pages: Active Power, Reactive Power and Apparent Power are replaced
                                       by the Powers page with the total active, reactive and apparent power measurements
                                     •  Ige/Rc current available with external toroid activated
                                     •  Power Controller page available with Power Controller function activated
                                     •  Load Shedding available with Load Shedding function activated
                                    Press the sides of the display to browse the pages; press the HOME key to quit.
                                           NOTE: each page can be set as the main page by pressing HOME, holding it for five seconds
                                           and confirming the message on the display



         Diagnosis bar and Alarm list The Diagnosis bar lists the faults detected by the unit. It shows a detail of each alarm for about two
                                    seconds.




                                    Figure 13
                                    Select the bar to access the Alarm List page, with the list of alarms present.














                                    Figure 14
                                           NOTE: the Alarm List page also appears when the iTEST button is pressed in the cases
                                           provided for and described on page 13
                                    Each signal is followed by an icon that identifies the type of alarm:
                                     Icon       Alarm type
                                                Alarm

                                                Warning, error or prealarm

                                                About

                                                Timing due to tripped protection


                                    The complete list of alarms is given on page 51.