ABB | SACE Emax 2
        Protections




       1 - Protections - Introduction



                 Operating principle The protection functions are available with all Ekip Touch models and versions.
                                    Each protection is associated with a different signal (current, voltages, frequencies, powers, etc) but the
                                    operating principle is the same:
                                      1.   If the signal measured exceeds the set threshold, the specific protection activates (prealarm and/
                                         or alarm).
                                      2.  The  alarm appears on the display and, after a period of time (timing t ), depending on the
                                                                                                   t
                                         protection parameters set, can convert into a trip command (TRIP) transmitted to the internal
                                         Trip coil of the CB.
                                           NOTE:
                                            •  if the signal measured drops below the set threshold before the trip time has elapsed, Ekip
                                              Touch quits the alarm and/or timing status and returns to the normal operating condition
                                            •  all protections have a default configuration: check the parameters and change to suit the
                                              installation requirements before putting into service
                                            •  to allow circuit-breaker tripping to be controlled by a specific protection, the protection
                                              itself must be enabled



                         References Many of the protection thresholds are displayed in two different quantities: absolute value and relative
                                    value.
                                    The relative value depends on the type of measurement:
                                     Type of protection  Reference          Description
                                     Current            In                  Nominal current of the Rating plug
                                     Voltage            Un                  Line-to-line voltage setting
                                     Frequency          fn                  Frequency setting
                                     Power              Sn                  √3 x In x Un













































       27 | © 2022 ABB |  1SDH001316R1002 - ECN000232533                           Protections | 1 - Protections - Introduction