Page 34 - ACB-E1.2-E2.2-E4.2-E6.2
P. 34
ABB | SACE Emax 2
ABB | SA CE Ema x 2
3 - Voltage protections
List
The Voltage protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in the remaining models
as additional SW package, are:
Th-
Name Type of protection Time Additional functions (2)
reshold
UV Minimum voltage Trip enable, Block
OV Maximum voltage Trip enable, Block
UV2 (1) Minimum voltage Trip enable, Block
OV2 (1) Maximum voltage Trip enable, Block
VU Voltage unbalance Trip enable, Block
Phase Sequence Phase sequence error
Further details about the protections are given in document 1SDH001330R1002.
(1) protections UV2 and OV2 are not available by default with Ekip G Touch. However, they can be integrated by requesting the relative SW
package
(2) Block configuration available via Ekip Connect
Summary table
Tolerance Calculation
ABB ANSI (5) Threshold Time Tolerance t (4)
threshold formula t (3) t
t
The best of the two values: ± 10% or ±
U8 = 0,5…1 Un t8 = 0,05...120 s
UV 27 ± 2 % (7) t = t8 40 ms (for set time < 5 s) / ± 100 ms (for
Step = 0,001 Un Step = 0,01 s t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
U9 = 1…1,5 Un Step t9 = 0,05…120 s
OV 59 ± 2 % (7) t = t9 40 ms (for set time < 5 s) / ± 100 ms (for
= 0,001 Un Step = 0,01 s t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
U15 = 0,5…1 Un t15 = 0,05…120 s
UV2 27 ± 2 % (7) t = t15 40 ms (for set time < 5 s) / ± 100 ms (for
Step = 0,001 Un Step = 0,01 s t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
U16 = 1…1,5 Un t16 = 0,05…120 s
OV2 59 ± 2 % (7) t = t16 40 ms (for set time < 5 s) / ± 100 ms (for
Step = 0,001 Un Step = 0,01 s t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
U14 = 2…90 % Step t14 = 0,5…60 s
VU (6) 47 ± 5 % t = t14 40 ms (for set time < 5 s) / ± 100 ms (for
= 1 % Step = 0,5 s t
set time ≥ 5 s)
Phase
Sequence 47 1-2-3 / 3-2-1
(3) calculation of t is valid for values which have exceeded the trip threshold of the protection
t
(4) tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
(5) ANSI / IEEE C37-2 codification
(6) protection not active if the higher of the voltages measured is less than 0.3 Un
(7) the trip unit considers 3% hysteresis for quitting alarm condition
32 | © 2022 ABB | 1SDH001316R1002 - ECN000232533 Protections