Page 24 - Application Guide Semiconductor Fuse Link
P. 24

3-phase controlled bridge rectifi er



                                                      VA         VB         VC



                                      Voltage



                                           0







                                               VB          VC          VA
                                           Id
                                                        1          3          5


                                                  4           6          2          4

                                                               line current, phase A


                                            Fig.17 Three-phase bridge rectifi er waveforms



                Location of fuses


                 In Fig.16 three possible locations for fuses are shown. For rectifi ers the principal choice is between
                 F1 and F2, as follows


                 F     in the converter legs, in series with the device. This gives the best possible protection of the
                  1
                       devices, with the smallest fuses.


                 F     in the a.c. supply lines. This requires only 3 fuses rather than 6 and may be a more
                  2
                       economical choice. However the line current is  2 times higher than the device current,
                       so higher ampere rated fuses are needed, compared with fuses in location F1. The higher
                                                                 2
                       ampere rated fuses have a higher clearing I t, which makes it somewhat more diffi cult
                       to protect the semiconductor devices. In critical cases it may not be possible to give proper
                       protection using fuses in location F .
                                                         2

                 F     are on the d.c. side. These fuses are normally used only when the converter is regenerative
                  3
                       and in conjunction with F  fuses. This will be discussed further in section 11.
                                                2

                External fault


                 If there is a sustained fault external to the bridge (short circuit on the d.c. side) this fault is cleared
                 by either a high speed d.c. circuit breaker or in most cases by the fuses when there is only 1 semi-
                 conductor per leg.


                 (a) In the case of fuses in the F1 position, the fuses clear the fault and protect the semi-conductors.
                                                                 2
                 Their total clearing I t is less than the withstand I t of the device (adjusted for the fault duration as
                                     2
                 previously discussed).



    24
   19   20   21   22   23   24   25   26   27   28   29