          Optional accessories for manual change-over switches

          Ordering information and technical data for auxiliary contacts




                                    —
                                    Auxiliary contact blocks for OT16...125F
                                    Snap-on mounting to the switch, IP20, max. 2 blocks/ side. Ith = 16 A, suitable for cable cross sections
                                    max. 2 x 2.5 mm². Simultaneous action with the main contacts.                      02
                                                                                                Delivery Weight/
                                    Suitable  Contact  Installation                             batch  unit
                                    for switches  functions  side  Type    Order code           pcs   kg
                                    OT_16...125F_C 1NO  Right  OA1G10      1SCA022353R4970      10    0.03
                                    OT_16...125F_C 1NC  Right  OA8G01      1SCA022744R2240      10    0.03
         OA1G01                     OT_16...125F_C 1NO  Left  OA7G10       1SCA022673R1140      10    0.03
         OA7G10
                                    OT_16...125F_C 1NC  Left  OA1G01       1SCA022353R4890      10    0.03
                                    OT63...125F3C  1NO+1NC  Either  OA2G11  1)  1SCA022379R8100  10   0.03
                                    1)  Not mountable on 4-pole change-over switches


                                    —
                                    Auxiliary contact blocks for OT160... 3200
                                    Mounting on the right side of the switch: Max. 4 auxiliary contact blocks/switch (totally 8 blocks). Types
                                    _AU have gold plated contacts for harsh environments and low operating voltages. Simultaneous action
                                    with the main contacts, IP20.
         OA1G10
         OA8G01
                                                                                                Delivery Weight/
                                    Suitable  Contact  Installation                             batch  unit
                                    for switches  functions  side  Type    Order code           pcs   kg
                                    OT_160…3200_ 1NO  Right  OA1G10        1SCA022353R4970      10    0.03
                                    OT_160…3200_ 1NC  Right  OA3G01        1SCA022456R7410      10    0.03
                                    OT_160…3200_ 1NO  Right  OA1G10AU      1SCA022436R7910      10    0.03
                                    OT_160…3200_ 1NC  Right  OA3G01AU      1SCA022819R5260      10    0.03





                                    Auxiliary contacts
                                    Technical data for auxiliary contacts according to IEC 60947-5-1, for OA1G_, OA2G_, OA3G_, OA7G_, OA8G_
          OA2G11                    AC15                             DC12                 DC13
                                    Ue         Ie         Ue         Ie         P         Ie         P
                                    V          A          V          A          W         A          W
                                    230        6          24         10         240       2          50
                                    400        4          72         4          290       0.8        60
                                    415        4          125        2          250       0.55       70
                                    690        2          250        0.55       140       0.27       70
                                    -          -          440        0.1        44        -          -

                                    Function tables
                                    Function table of OT160…3200, OT160...800_Y and OTM160…2500 auxiliary contacts / Switch I (max. 2+2)
                                    Handle position    Main contacts      OA1G10 NO          OA3G01 NC
                                    I                  closed             closed             open
                                    0                  open               open               closed
                                    II                 closed             open               closed
                                    Function table of OT160…3200, OT160...800_Y and OTM160…2500 auxiliary contacts / Switch II (max. 2+2)
                                    Handle position    Main contacts      OA1G10 NO          OA3G01 NC
                                    I                  closed             open               closed
                                    0                  open               open               closed
                                    II                 closed             closed             open