42               ABB  TRANSFER AND CHANGE-OVER SWITCHES




          —
          Manual change-over switches

          Technical data for OT16...125_C



          Switch size                                                 OT16_  OT25_  OT40_  OT63_  OT80_  OT100_  OT125_
          Data according to IEC 60947-3
          Rated insulation voltage and rated            Pollution    V  750  750  750   750   750   750   750
          operational voltage AC20/DC20                 degree 3
          Dielectric strength                           50 Hz 1min.  kV  6  6     6     6     6     6     6
          Rated impulse withstand voltage                        kV   8     8     8     8     8     8     8
          Rated thermal current and rated    / ambient 40°C   In open air   A  25  32  40  63  80   115   125
          operational current AC20/DC20  / ambient 40°C   In enclosure  A  25  32  40   63    80    115   125
                                        / ambient 60°C   In enclosure  A  20  25  32    50    63    80    100
          ..with minimum conductor cross section        Cu       mm²  4     6     10    16    25    35    50
          Rated operational current, AC-21A             up to 500 V  A  16  25    40    63    80    100   125
                                                        690 V    A    16    25    40    63    80    100   125
          Rated operational current, AC-22A             up to 500 V  A  16  25    40    63    80    100   125
                                                         690 V   A    16    25    40    63    80    100   125
          Rated operational current, AC-23A             up to 415 V  A  16  20    23    63    75    80    90
                                                        440 V    A    16    20    23    63    65    65    78
                                                        500 V    A    16    20    23    45    58    60    70
                                                        690 V    A    10    11    12    20    20    40    50
          Rated operational current / poles in series, DC-21A  up to 48 V  1)  A   16/1   25/1  32/1  63/1  80/1  100/1  125/1
                                                        110 V    A    16/2   25/2  32/2  63/2  80/2  100/2  125/2
                                                        220 V    A    16/3   25/3  32/3  63/4  63/4  100/4  100/4
                                                        500 V    A    16/4   16/4  16/4  16/4  16/4  -    -
          Rated operational current / poles in series, DC-22A  up to 48 V  1)  A  16/1   25/1  32/1  63/1  80/1  100/1  125/1
                                                        110 V    A    16/2   25/2  32/2  63/2  80/2  100/2  125/2
                                                        220 V    A    16/3   25/3  32/4  45/4  45/4  63/4  80/4
                                                        440 V    A    10/4   10/4  10/4  10/4  10/4
          Rated operational current / poles in series, DC-23A  up to 48 V  1)  A  16/1   25/1  32/1  63/1  80/1  100/1  125/1
                                                        110 V    A    16/2   25/2  32/2  63/2  80/2  100/2  125/2
                                                        220 V    A    16/4   25/4  32/4  45/4  45/4  63/4  63/4
                                                        440 V    A    10/4   10/4  10/4  10/4  10/4
          Rated operational power, AC-23A  2)           230 V    kW   3     4     5.5   11    22    22    22
          The kW-ratings are accurate                   400...500 V  kW  7.5  9   11    22    37    37    45
          for 3-phase 1500 R.P.M. standard
          asynchronous motors                           690 V    kW   7.5   9     11    15    18.5  37    45
          Rated breaking capacity in category AC-23     up to 415 V  A  128  160  184   360   640   640   720
                                                        500 V    A    128   160   184   360   464   480   560
                                                        690 V    A    80    88    96    160   160   320   400
          Rated conditional short-circuit current I p (r.m.s.)   Ip (r.m.s.) 50 kA, 415 V  îc (peak)  kA  6.5  6.5  6.5  13  13  16.5  16.5
          and corresponding max. allowed cut-off current î c   Max. OFA_ fuse size   gG/aM  A/A  40/32  40/32  40/32  100/80  100/80  125/125 125/125
          (peak) value. The cut-off current î c refers to values
          listed by fuse manufacturers (single phase test acc.   Ip (r.m.s.) 100 kA, 500 V  îc (peak)  kA  -  -  -  17  17  -  -
          to IEC60269).                 Max. OFA_ fuse size   gG/aM  A  -   -     -     100/80  100/80  -  -
          Rated short-time withstand current  I cw (r.m.s.)  690 V 1s  kA  0.5  0.5  0.5  1.5  1.5  2.5   2.5
          Rated short-time making capacity  3)  I cm (peak)  690 V  kA  0.7  0.7  0.7   1.4   2.1   3.6   3.6
          Power loss / pole             With rated current       W    0.3   0.6   1.6   2.8   4.5   4.0   6.3
          Mechanical endurance          Number of oper. cycles  4)  Cycles  10 000  10 000  10 000  10 000  10 000  10 000  10 000
          Cable size                    Cu-wire size suitable    mm²  0.75-10  0.75-10  0.75-10  1.5-35  1.5-35  10-70  10-70
                                        for terminal clamps      AWG  18-8  18-8  18-8  14-4  14-4  8-00  8-00
          Terminal tightening torque    Counter torque required  Nm   0.8   0.8   0.8   2     2     6     6
          Operating torque              Typical for 3-pole switches  Nm  1  1     1     1.2   1.2   2     2
          Weight without accessories    3-pole switch            kg   0.25  0.25  0.25  0.64  0.64  0.90  0.90
                                        4-pole switch            kg   0.31  0.31  0.31  0.70  0.70  1.18  1.18
          Data according to UL508 (Listed)
          Current                                                A    16    25    40    60    80    -     -
          Horsepower, 3-phase                           200 V    HP   3     7.5   10    15    20    -     -
                                                        208 V    HP   3     7.5   10    15    20    -     -
                                                        240 V    HP   5     7.5   10    15    20    -     -
                                                        480 V    HP   10    15    20    30    40    -     -
                                                        600 V    HP   10    20    25    30    40    -     -
          1)  Below 48 V, two poles in parallel up to OT80 are recommended particularly in polluted atmosphere
          2)  These values are given for guidance and may vary according to the motor manufacturer
          3)  Short circuit duration >50ms, without fuse protection
          4)  Operating cycle: O - I - O - II - O